GOST 31173-2003

UDC 692.81-034.14(083.74):006.354

EURASIAN COUNCIL FOR STANDARDIZATION, METROLOGY AND CERTIFICATION (EACC) INTERSTATE STANDARD STEEL DOOR BLOCKS Specifications Steel doors Specifications

OKS 91.060.50

Introduction date - 2004-03-01

Foreword

The Eurasian Council for Standardization, Metrology and Certification (EASC) is a regional association of national standardization bodies of states that are members of the Commonwealth of Independent States. In the future, national standardization bodies of other states may join the EASC. The EASC operates the Interstate Scientific and Technical Commission for Standardization, Technical Regulation and Certification in Construction (MNTKS), which has been granted the right to adopt interstate standards in the field of construction. The goals, basic principles and basic procedure for carrying out work on interstate standardization are established by GOST 1.0-92 “Interstate standardization system Basic provisions” and MSN 1.01-01-96 “System of interstate regulatory documents in construction. Basic Provisions»

About the standard

1 DEVELOPED by the Center for Certification of Window and Door Equipment and the Federal State Unitary Enterprise Central Design and Technology Bureau (FSUE TsPKTB of the Gosstroy of Russia) with the participation of the Academy of Safety and Law and the company Abloy Oyu, Bjerkboda Plant, Finland 2 INTRODUCED by the Gosstroy of Russia 3 ADOPTED by the Interstate Scientific and Technical Commission for Standardization, Technical Regulation and Certification in Construction (ISTCS) on May 14, 2003 Voted to accept:

4 INTRODUCED FOR THE FIRST TIME 5 Entered into force on March 1, 2004 as a state standard Russian Federation Decree of the Gosstroy of Russia dated June 20, 2003 No. 76 Information on the entry into force (termination of action) of this standard and changes to it on the territory of the above states is published in the indexes of national (state) standards published in these states. Information about changes to this standard is published in the index (catalog) "Interstate standards", and the text of the changes - in the information indexes "Interstate standards". In case of revision or cancellation of this standard, the relevant information will be published in the information index "Interstate Standards".

1 area of ​​use

This standard applies to steel door blocks with installed locking devices (hereinafter referred to as door blocks or products) for buildings and structures for various purposes. The standard does not apply to door units for special purposes in terms of additional requirements to fire safety, explosion and bullet resistance, exposure to aggressive environments, etc., as well as to the door blocks of protective cabins in accordance with the current regulatory documentation. The scope of specific types of products is established depending on the operating conditions in accordance with the current building codes and regulations, taking into account the requirements of this standard. The standard can be applied for certification purposes.

References to the following standards are used in this document: GOST 9.032-74 ESZKS. Paint coatings. Groups. Technical requirements and designations GOST 9.301-86 ESZKS. Metallic and non-metallic inorganic coatings. General requirements GOST 9.303-84 ESZKS. Metallic and non-metallic inorganic coatings. General requirements for the selection of GOST 9.401-91 ESZKS. Paint coatings. General requirements and accelerated test methods for resistance to climatic factors GOST 9.402-80 ESZKS. Paint coatings. Preparation of metal surfaces before painting GOST 99-96 Rotary cut veneer. Specifications GOST 166-89 Calipers. Specifications GOST 380-94 Carbon steel of ordinary quality. Grades GOST 427-75 Measuring metal rulers. Specifications GOST 538-2001 Lock and hardware products. General specifications GOST 1050-88 Rolled section calibrated, with a special surface finish from quality carbon structural steel. General specifications GOST 2140-81 Visible defects of wood. Classification, terms and definitions, measurement methods GOST 2977-82 Sliced ​​veneer. Specifications GOST 4598-86 Wood fiber boards. Specifications GOST 5089-2003 Locks and latches for doors. Specifications GOST 5264-80 Manual arc welding. Connections are welded. Main types, structural elements and dimensions GOST 5632-72 High-alloy steels and corrosion-resistant, heat-resistant and heat-resistant alloys. Grades GOST 7016-82 Products made of wood and wood materials. Roughness parameters

surfaces GOST 7502-98 Measuring metal tapes. Specifications GOST 8026-92 Calibration rulers. Specifications GOST 8242-88 Profiled parts made of wood and wood materials for construction. Specifications GOST 8713-79 Submerged arc welding. Connections are welded. Basic types, structural elements and dimensions GOST 9416-83 Building levels. Specifications GOST 10354-82 Polyethylene film. Specifications GOST 11533-75 Automatic and semi-automatic submerged arc welding. Connections are welded at acute and obtuse angles. Main types, structural elements and dimensions GOST 11534-75 Manual arc welding. Connections are welded at acute and obtuse angles. Main types, structural elements and dimensions GOST 14771-76 Gas-shielded arc welding. Connections are welded. Main types, structural elements and dimensions GOST 15140-78 Paintwork materials. Methods for determining adhesion GOST 21778-81 Accuracy assurance system geometric parameters in construction. Basic provisions of GOST 21779-82 System for ensuring the accuracy of geometric parameters in construction. Technological tolerances GOST 21780-83 System for ensuring the accuracy of geometric parameters in construction. Accuracy calculation GOST 23118-99 Construction steel structures. General specifications GOST 23518-79 Arc welding in shielding gases. Connections are welded at acute and obtuse angles. Basic types, structural elements and dimensions GOST 25347-82 Basic standards of interchangeability. ESDP. Tolerance fields and recommended fits GOST 26433.0-85 System for ensuring the accuracy of geometric parameters in construction. Rules for performing measurements. General provisions GOST 26433.1-89 System for ensuring the accuracy of geometric parameters in construction. Rules for performing measurements. Prefabricated elements GOST 26602.1-99 Window and door blocks. Methods for determining resistance to heat transfer GOST 26602.2-99 Window and door blocks. Methods for determining air and water permeability GOST 26602.3-99 Window and door blocks. Method for determining sound insulation GOST 30778-2001 Gaskets sealing from elastomeric materials for window and door blocks. Specifications GOST 30971-2002 Mounting seams for adjoining window blocks to wall openings. General specifications GOST 30972-2002 Glued wooden blanks and parts for window and door blocks. Specifications

3 Terms and definitions

Terms and definitions used in this standard are given in Annex A.

4 Classification and symbol

4.1 Products are classified according to the following criteria: purpose; options design; type of finish; performance indicators; mechanical characteristics; protective properties. 4.1.1 By purpose, door blocks are divided into: external (entrance to buildings, premises, as well as vestibules); internal (entrance to the apartment and others intended for operation inside the building). 4.1.2 According to the design options, door blocks are subdivided: according to the design of the box: with a closed box; with U-shaped box;

with a U-shaped box with an additional threshold; according to the number of canvases (including non-opening ones), direction and type of opening: single-floor (left and right opening); double-sided (including with canvases of different widths); with non-opening horizontal or vertical inserts; with opening inside the room; with outward opening; according to the number of sealing circuits in the porch: with one circuit; with two or more circuits. 4.1.3 According to the type of finish, door blocks are divided into: painted with paint and varnish and powder materials; lined with leather (artificial or natural) and insulation; pasted over with decorative film materials; lined with wood or wood-based materials (including those with natural or synthetic veneer); finished with glass (mirror) materials; trimmed with decorative metal cladding; combined (including from other materials). Note - By agreement with the customer, it is allowed to use other types of finishes. 4.2 In terms of performance, door blocks are classified according to the reduced resistance to heat transfer, air and water permeability, and sound insulation. 4.2.1 In terms of the reduced heat transfer resistance of the leaf, the door blocks are divided into classes: 1 - with a reduced heat transfer resistance of 1.0 m2 × °C / W or more; 2 - with reduced resistance to heat transfer from 0.70 to 0.99 m2 × °C/W; 3 - with reduced resistance to heat transfer 0.40 - 0.69 m2 × °C / W. Note - Door blocks with a reduced heat transfer resistance of less than 0.40 m2 × ° C / W are not subject to classification according to this indicator.

4.2.2 In terms of air and water permeability, door blocks are divided into classes given in table 1. Table 1

Notes 1 The indicator of the limit of water resistance - for entrance door blocks to buildings and premises from the street. 2 Door blocks with an air permeability of more than 27 m3/(h×m2) are not subject to classification according to this indicator. 4.2.3 In terms of sound insulation Rw, door blocks are divided into classes: 1 - with a reduction in airborne noise of 32 dB or more; 2 - » » » » 26-31 dB; 3 - » » » » 20-25 dB. Note - Door blocks with sound insulation less than 20 dB are not subject to classification according to this indicator.

4.3 Door blocks are classified according to the main mechanical characteristics into the strength classes given in table 2. Table 2

NOTES 1 The class of the door unit is determined by the worst result of all tests. 2 An example of determining the strength class when testing for resistance to a static load acting perpendicular to the plane of the web in the free corner zone is given in Appendix D.

4.4 Depending on the presence of security properties, door blocks are divided into: standard door blocks, equipped with class III-IV locks according to GOST 5089, blocking anti-removable devices; reinforced door blocks equipped with class III-IV locks according to GOST 5089, reinforced hinges, locking anti-removable devices, multi-bar locks with perimeter locking, with strength characteristics not lower than class M2; protective door blocks - door blocks of reinforced design, with strength characteristics not lower than class M1 and meeting the requirements established in Appendix B. 4.5 The structure of the symbol for door blocks:

Examples of symbols: DSV DKN 2100-1270 M3 GOST 31173-2003 - internal steel door block, two-leaf, with a closed frame, with doors opening outwards, standard design, strength class - M3, height 2100 mm, width 1270 mm. DSN PPVn 1-2-2 M2 U 2300-900 GOST 31173-2003 - steel outer door block, single-floor right-hand execution, with a threshold, with opening the leaf inwards, class in terms of reduced resistance to heat transfer - 1, class in terms of air and water permeability - 2, class in terms of sound insulation - 2, strength class - M2, reinforced version, height 2300 mm, width 900 mm. When placing an order for manufacturing (delivery) and a passport, it is recommended to indicate: a variant of a constructive solution, including a description of the filling of the door leaf; a drawing indicating the scheme for opening the canvases and the design of the door block; type and brand of door devices and class of locks; type of finish, box width and other requirements as agreed between the manufacturer and the customer. For export-import deliveries, it is allowed to use a different structure of the symbol specified in the agreement (contract).

5 Technical requirements

5.1 General provisions and design requirements 5.1.1 Products must comply with the requirements of this standard and be manufactured according to the design and technological documentation approved in the prescribed manner. 5.1.2 Cloths of door blocks are a structure welded from steel sheets and rectangular or bent profiles. It is allowed to use the design of "bent box" type canvases, while steel sheets are recommended to be welded together. In the production of welding work, it is recommended to use welding in a shielding gas environment. The places of welding points are set in the working documentation. 5.1.3 Corner joints of profiles are recommended to be connected by means of welded joints. Other types of joints are allowed, corresponding to or exceeding the strength of welded ones. Options for door leafs and examples of door block designs are shown in Figures 1-7.

1 - upper locking crossbar; 2 - upper link of the main lock; 3 - web frame (welded steel profiles); 4 - places for attaching the internal "hatch"; 5 - valve; 6 - the place of attachment of the upper link; 7 - crossbar of the deadbolt of the lever lock; 8 - latch; 9 - deadbolt of the cylinder lock; 10 - lower link of the main lock; 11 - places for fastening the finish; 12 - internal cavity for filler; 13 - vertical thrust guide; 14 - lower locking crossbar; 15 - mounting "eye"; 16 - threshold; 17 - hole for anti-removable crossbar (pin); 18 - anti-removable passive crossbar (pin); 19 - mounting anchor; 20 - box (frame); 21 - combined lever-cylinder lock; 22 - inner steel sheet; 23 - outer steel sheet; 24- loop knot;

25 - peephole

Figure 1 - An example of the design of a door block, the leaf of which is welded from two steel sheets and steel profiles, the box (frame) is made of a bent steel profile

Door leaf with two steel sheets, steel box profiles and honeycomb core

Canvas with outer steel sheet and inner sheet from fiberboard, with profiles of complex cross-section and filling from wood or mineral insulation

Door leaf of "bent box" type, with U-shaped steel profiles and foam filling

Door leaf with steel outer sheet and fiberboard inner sheet, steel angle profiles with timber bars and foam core

Figure 2 - Examples of door leaf designs

Figure 3 - An example of the design of a door block welded from steel sheets and profiles (with filling the middle profile of the frame and leaf with wood and foam material)

Figure 4 - An example of the construction of a door block welded from steel sheets and profiles, with natural wood cladding

Figure 5 - An example of the construction of a two-leaf door block with a lining of wood or wood-based materials (horizontal section)

Figure 6 - Examples of door leaf structures welded from two flat steel sheets and steel profiles (a) and a bent box type door leaf (b) with vertical reinforcing profiles

Figure 7 - Examples of the design of a door leaf welded from steel profiles, with vertical and horizontal reinforcing profiles and installed locks (a) and a door frame (b)

Boxes (frames) are made from a bent profile with a thickness of at least 1.5 mm or from a rectangular profile with a cross section of at least 40x50 mm. Boxes (frames) and door leafs are manufactured according to at least 15th grade of accuracy in accordance with GOST 25347.

5.1.4 It is recommended to use vertical and horizontal reinforcing profiles (multipliers) in door leaf structures. It is recommended to use at least two vertical and horizontal reinforcing profiles. It is allowed to place reinforcing profiles at an angle between vertical ones (inclined profiles). Horizontal reinforcing profiles are recommended to be placed in the loop zone or in the zone of anti-removable devices. Examples of the location of reinforcing profiles in the door leaf are shown in Figure 8.

Figure 8 - Examples of the location of reinforcing profiles in the door leaf

5.1.5 It is allowed to use butted sheet blanks welded along reinforcing profiles instead of an internal solid steel sheet, while the places of welding points are set in the design documentation. As an inner sheet, it is allowed to use solid fiber boards in accordance with GOST 4598 or other solid sheet materials that provide sufficient strength.

5.1.6 To repair locks and latches at their installation site, it is recommended to provide a “hatch” in the inner sheet, which is attached to mechanical ties. 5.1.7 Locking devices (locks, latches, additional bolts) are recommended to be fixed on screws through special pads and clamping brackets with threaded threads. The fastening of the locking devices must be strong and reliable, excluding their spontaneous displacement during operation. It is not recommended to fix the lock by welding (in case of technological necessity of using welding, the possibility of thermal influence on fusible plastic and other parts of the lock should be taken into account). The lock must be installed in accordance with the requirements of the design documentation so that during the operation of the door unit there are no compressive or bending loads on the lock. 5.1.8 It is recommended to install at least two contours of sealing gaskets in the structures of external and entrance door blocks to the apartment (to increase sound insulation and resistance to heat transfer). Sealing gaskets must be installed around the entire perimeter of the porch. Gaps in the joints of the gaskets are not allowed. The fit of the gaskets must be tight. Sealing gaskets for external door units must be resistant to climatic and atmospheric influences and tested for durability in testing centers accredited to carry out such tests. 5.1.9 The requirements of this standard apply to door blocks with an area not exceeding 9 m2, while the height of opening door panels is recommended not to exceed 2200 mm, and the width - not more than 1200 mm. It is allowed to use non-opening horizontal and vertical canvas-inserts. The recommended weight of door panels is no more than 250 kg (calculated indicator). The manufacture of door blocks (cloths) with an area, weight and dimensions exceeding the specified values ​​must be confirmed by the results of laboratory tests or additional strength calculations in accordance with current building codes. Note - Largest dimensions leafs of door blocks of specific types, depending on the weight of the leaf, section modulus of the profiles of the frame of the leaf, the rigidity of the section of the middle part of the leaf (including the outer and inner lining, filling, reinforcing profiles), the location (and types) of hinges and locking devices should be given in the design manufacturer's documentation. 5.1.10 The location and dimensions of the holes for installing locks and other locking devices are set in the design documentation, taking into account the requirements of GOST 5089. 5.1.11 It is recommended to protect the places of the holes intended for the bolt entry with special boxes. The boxes are welded into the profile of the box (frame) so that they do not interfere with the normal movement of the deadbolt bolts. It is allowed to make holes for the entry of bolts in the door frame. In this case, the dimensions of the hole should be 2-3 mm larger than the corresponding cross-sectional dimensions of the bolt. In the closed position, the bolt of the lock must enter the door frame to a depth of at least 22 mm. 5.1.12 In the design of products on the hinge side, it is recommended to provide anti-removable passive crossbars (pins). The pins must be firmly installed in the frame of the door leaf or in the frame by welding, pressing or riveting. It is allowed to use other types of fastening of anti-removable pins that do not reduce their strength properties. The size, number and location of the anti-detachable pins are specified in the working documentation, while it is recommended to install the anti-detachable pins in the loop area to ensure the greatest protection. 5.1.13 To carry out the installation of the door block in the wall opening, mounting "lugs" are welded onto the profile of the box (frame). The size, number and location of the mounting "lugs" are set in the working documentation. It is allowed to use other designs of fasteners that provide the necessary rigidity and strength when mounting the door block. 5.1.14 It is recommended to use heat and sound insulating materials as the internal filling of door panels, for example, mineral wool, basalt wool, foam plastic or other materials according to regulatory documentation (RD). Filling is laid tightly, without voids. 5.1.15 Products must be safe to use. The safety conditions for the use of products of various designs are established in the design documentation (for example, door blocks on escape routes are recommended to be equipped with anti-panic devices). Products must be designed for operating loads in accordance with current building codes. When designing and manufacturing products, calculation programs or calculation methods for determining the strength characteristics of products should be used. 5.1.16 Polymeric and synthetic materials used for filling and finishing door panels must have sanitary safety conclusions provided for by applicable law and executed in the prescribed manner

5.2 Dimensions and requirements for limit deviations 5.2.1 Overall dimensions and architectural drawings of door blocks are set in the design and technical documentation (order, supply contract) for the manufacture of products. The nominal dimensions of parts of product assemblies, sections of profiles and gaps, the dimensions of the location of devices, hinges and holes are set in the technical documentation for their manufacture. 5.2.2 Limit deviations of the nominal overall dimensions of products should not exceed ±3.0 mm. 5.2.3 Limit deviations of the nominal dimensions of product elements, gaps under the overlay, dimensions of the arrangement of door devices and hinges should not exceed the values ​​specified in Table 3.

Table 3 In millimeters

Note - The values ​​of the maximum deviations of the dimensions of the gaps under the overlay are given for closed canvases with installed sealing gaskets. The difference in the lengths of the diagonals of rectangular canvases with an area of ​​​​1.5 m2 or less should not exceed 2.0 mm, and with an area of ​​\u200b\u200bover 1.5 m2 - 3.0 mm.

5.2.4 The difference between the front surfaces (sag) in welded fillet joints shall not exceed 2.0 mm. 5.2.5 The sagging of the canvases in the assembled product for the construction of door blocks with a threshold should not exceed 2.0 mm per 1 m of width. 5.2.6 Deviations from the straightness of the edges of sheets and boxes should not exceed 1.0 mm per 1.0 m of length. Note - The flatness of the door panels is controlled by measuring the straightness of their edges and the size of the gaps under the overlay. 5.2.7 The accuracy of geometrical parameters is calculated in accordance with GOST 21778, GOST 21779, GOST 21780, taking into account the features of specific structures and technological conditions of manufacture and installation. 5.2.8 The dimensions of the welds must correspond to their working sections established in the technical documentation. Deviations of weld dimensions from the specified ones should not exceed the values ​​specified in GOST 5264, GOST 8713, GOST 11533, GOST 11534, GOST 14771, GOST 23518. 5.2.9 Nominal diameters of holes for bolted connections and maximum deviations from them, established depending on the method formation and type of bolted connection are accepted in accordance with GOST 23118.

5.3 Characteristics 5.3.1 Operational parameters of door units are given in Table 4. Table 4

Note - The need to use performance indicators marked with an "*" is established in the design and technical documentation based on the purpose of the door blocks.

5.3.2 It is recommended to establish the performance indicators of door blocks for a specific purpose in the design documentation for construction (reconstruction) and confirm the results of tests at testing centers accredited for their right to conduct them.

5.3.3 Door blocks, depending on the strength class, must withstand the action of static loads in accordance with the requirements of table 5. Table 5

5.3.4 Door units, depending on the strength class, must withstand the action of dynamic loads (impact on an obstacle - opening angle limiter, door slope, etc. when opening the leaf) in accordance with the requirements of Table 6. Table 6

5.3.5 Door blocks, depending on the strength class, must withstand impact with a soft inelastic body in accordance with the requirements of table 7. Table 7

5.3.6 The force applied to the door leaf when closing until the required compression of the sealing gaskets should not exceed 140 N, while in the closed position the latch and the deadbolt of the lock should work without jamming. The force required to open the door leaf must not exceed 100 N (ergonomic requirements). 5.3.7 In the case of using artificial or natural leather or wood (wood-based materials, including those with natural or synthetic veneer) for cladding door panels, the cladding material must withstand without destruction an impact by a metal ball weighing 1 kg from a height of 1 m. 5.3. 8 Appearance of products: color, permissible surface defects of facing materials and painted elements (risks, scratches, etc.) must correspond to standard samples approved by the head of the manufacturer. Differences in color, gloss and surface defects that are visible to the naked eye from a distance of 0.6 - 0.8 m in natural light of at least 300 lux are not allowed. 5.3.9 Welded joints must be strong and satisfy visually controlled requirements: the weld metal and the boundary zone must not have cracks. Seam craters at the places where welding stops (ends) must be overcooked (welded); seams should have a smooth or evenly scaly surface without sharp transitions to the base metal; welds must be tight along the entire length and not have burns, constrictions, welds, lack of penetration, slag inclusions, etc. 5.3.10 The tensile strength of the welded joint metal must not be lower than the requirements for the base metal. Characteristics of categories and quality level of welded joints - according to GOST 23118.

5.4 Requirements for materials and components (including gaskets) 5.4.1 Materials and components used for the manufacture of door blocks must comply with the requirements of standards, specifications, technical certificates approved in the prescribed manner. 5.4.2 Materials and components used for the manufacture of door blocks must be resistant to climatic influences. 5.4.3 The surfaces of steel elements of boxes and sheets should not have cracks, mechanical damage, pits, distortions, rust. On the front surfaces of steel elements, slight local depressions, risks, waviness up to 0.5 mm deep are allowed, which do not reduce the functional properties and quality of products. 5.4.4 Steel parts of structures should be made of steel grades that ensure the strength characteristics of structural elements, welded, bolted and other connections, depending on the nature and conditions of their work. Steel elements are recommended to be made of steel grade not lower than St3kp2 in accordance with GOST 380, rolled sections in accordance with GOST 1050 or high-alloy steel in accordance with GOST 5632. water penetration. Sealing gaskets must be installed continuously around the entire perimeter of the porch. 5.4.6 Glued wooden cladding panels must meet the requirements of GOST 30972, profile molded wooden parts - GOST 8242.

5.5 Requirements for hinges, locks and other locking devices 5.5.1 In the manufacture of products, locking and auxiliary devices and hinges are used, specially designed for use in metal door blocks. Examples of designs of hinges and locks are given in Appendix B. The type, number, location and method of fastening of locking devices and hinges are set in the working documentation based on the size and weight of the opening elements of the product, as well as the operating conditions of the door blocks. Cloths of door blocks weighing more than 200 kg, as well as products used in public buildings (schools, hospitals, etc.), are recommended to be hung on three hinges. The recommended location of the middle hinge is 150-200 mm below the top one. 5.5.2 For hanging canvases on a box (frame), it is recommended to use overhead bearing or other hinges with the ability to adjust in different planes. It is recommended to fasten hinges to canvases and boxes using mechanical ties or by continuous welding. It is allowed to use other types of fastening loops, allowing to provide the necessary strength of the structure. 5.5.3 Locks of at least class III in accordance with GOST 5089 must be installed in door blocks. Locks must comply with the requirements of GOST 538 and GOST 5089. It is recommended to simultaneously install locks with lever and cylinder mechanisms, as well as locks with recoding secret mechanisms in the door block. To improve the protective properties of door blocks, it is recommended to use multi-bolt locks with locking along the perimeter of the door block or locks with rods with additional locking in the upper and lower horizontal frame profiles. To avoid clogging of the hole for the lower vertical bolt included in the bottom profile of the box, it is recommended to use deviators. 5.5.4 Depending on the purpose of the door blocks in the project documentation, as well as when placing orders, it is necessary to provide for the complete set of products with latches, door closers (closers), opening angle limiters (stops), eyes, chains, etc. 5.5.5 Locking devices must ensure reliable locking of the opening elements of the products. Opening and closing should be easy, smooth, without jamming. 5.5.6 The design of the locking devices and hinges shall ensure tight and uniform crimping of gaskets along the entire contour of the seal in the porches. 5.5.7 Door appliances and fasteners must meet the requirements of GOST 538 and have a protective and decorative (or protective) coating in accordance with GOST 9. 303. 5.5.8 In cases where door blocks are installed in public premises (kindergartens, schools, hospitals), it is recommended to use anti-panic devices, smoke detectors and other devices that allow for quick evacuation. 5.5.9 When accepting work, the keys must be handed over to the customer in a sealed package against his signature on receipt.

5.6 Requirements for product finishing 5.6.1 The quality of the finish, as well as the requirements for the finishing coating (cladding) may be set by agreement between the manufacturer and the consumer in the contract (order) for the manufacture (supply) of products. In this case, it is allowed to evaluate the quality of the finish according to standard samples agreed with the customer. 5.6.2 As finishing materials, artificial and natural leather, decorative films, MDF boards (with natural or synthetic veneer, smooth or milled), wood, mirrors, plastic, fiberboard, paint and varnish and other materials are used in accordance with the requirements of ND. When choosing facing materials, the operating conditions of the products should be taken into account. Options for finishing door blocks are given in Appendix B. 5.6.3 The metal surfaces of the parts before applying paint and varnish and polymer coatings must comply with GOST 9.402. Requirements for paint coatings - in accordance with GOST 9.401, designation of coatings - in accordance with GOST 9.032, coating class is not lower than IV. 5.6.4 The quality of surfaces with a finished paint and varnish coating must comply with the requirements established in GOST 9.032. In this case, the first layer should be applied with a primer paint, and subsequent layers with protective and decorative paints and varnishes. 5.6.5 The front surfaces of the products should not have cracks, burrs, mechanical damage. The requirements for front surfaces are set in the manufacturer's technical documentation and / or in supply contracts, taking into account GOST 9.301 and GOST 9.032. Non-facial surfaces of products may have depressions, risks, waviness and other surface defects that do not reduce the functional properties and quality of products. Hole edges must be free of burrs and burrs. 5.6.6 Color (tone) and degree of gloss (gloss, dullness) of the finishing coating must correspond to standard samples approved by the head of the manufacturer and agreed with the customer. 5.6.7 Paint and varnish coatings must have adhesion strength (adhesion) with the surface to be trimmed of at least 2 points according to the method of lattice cuts in accordance with GOST 15140. . 5.6.9 Protective and protective and decorative coatings must be resistant to temperature and humidity operational impacts. 5.6.10 Facing of product sheets is made from MDF boards according to ND or from various types of wood. MDF boards can be finished with sliced ​​veneer according to GOST 2977, peeled veneer according to GOST 99 or synthetic veneer according to ND. It is allowed to use milled or smooth MDF boards. Examples of the architectural design of finishing door panels with MDF boards are given in Appendix B. 5.6.11 The front surfaces of wood parts used for finishing door panels should not have processing defects and wood defects, with the exception of curls, pilosity, eyes, fiber inclination up to 5% in accordance with GOST 2140. The recommended roughness of the front surfaces of wood parts Rm is not more than 60 microns in accordance with GOST 7016, the moisture content of wood should be in the range from 8 to 12%. 5.6.12 The design of fastening of facing parts made of wood and board materials to steel elements door blocks should provide the ability to compensate for their temperature and humidity deformations. The shape and dimensions of the sections of the facing profiles adjacent to the steel surfaces of the external products must provide a minimum area of ​​​​contact with these surfaces, as well as the possibility of ventilation of the cavity between them, otherwise the contacting surfaces must be protected by paintwork or other protective materials. 5.6.13 Adhesive materials used when lining door panels with artificial or natural leather, as well as decorative films, must provide sufficient adhesion strength, while non-glued areas, folds, waviness and other appearance defects are not allowed.

5.7 Completeness and marking 5.7.1 The completeness of products when they are delivered to the consumer must comply with the requirements established in the contract (order). Door units should be delivered assembled with locking devices installed. By agreement with the consumer, the set of products may also include closers (closing regulators), opening angle limiters and other door devices. The set of keys must be handed over to the customer in a sealed form against the signature of the customer (buyer). 5.7.2 The scope of delivery should include a document on quality (passport) and instructions for the operation of products, including recommendations for installation. 5.7.3 Each product is marked with a waterproof marker or label indicating the name of the manufacturer, the brand of the product, the date of its manufacture and (or) the order number, a sign (stamp) confirming the acceptance of the product by technical control. 5.7.4 The door devices included in the product must be marked in accordance with the ND for this product.

6 Acceptance rules

6.1 Products must be accepted by the manufacturer's technical control service for compliance with the requirements of this standard, as well as the conditions specified in the contract for the manufacture and supply of products. Confirmation of acceptance of products by the technical control service of the manufacturer is the execution of documents on the acceptance (quality) of products. Products are accepted in batches or individually. When accepting products at the manufacturing plant, a lot is taken as the number of products manufactured within one shift and issued with one quality document. The batch size can be taken as the number of products of the same design, manufactured according to one order. 6.2 The requirements for product quality established in this standard are confirmed by: incoming inspection of materials and components; operational production control; acceptance control of finished products; control acceptance tests of a batch of products, conducted by the quality control service of the manufacturer; periodic and certification tests of products in independent testing centers; qualification tests. 6.3 The procedure for conducting incoming control and operational production control at workplaces is established in the technological documentation. If the manufacturer completes the door blocks with components of its own manufacture, then they must be accepted and tested in accordance with the requirements of the regulatory documentation for these products. 6.4 Acceptance control of the quality of finished products is carried out by the method of continuous control. The list of controlled indicators is given in table 8. Finished products that have passed acceptance control are marked. Products that have not passed the acceptance control for at least one indicator are rejected. Table 8

* Test type I - acceptance tests during acceptance control; test type II - acceptance tests conducted by the quality service of the manufacturer; test type III - periodic tests carried out in independent test centers. ** Controlled nominal dimensions for test type II are set in the technological documentation.

6.5 Each batch of products undergoes control acceptance tests conducted by the quality service of the manufacturer. The list of controlled indicators and the frequency of control are given in Table 8. For testing, samples of door blocks are taken from a batch of products by random selection in the amount of 3% of the batch volume, but not less than 3 pcs. If there are less than 3 products in a batch, each product is subjected to control. In the event of a negative test result for at least one indicator on at least one sample, a re-check of the quality of products is carried out on a double number of samples for the indicator that had a negative test result. If a discrepancy between the indicator and the established requirements is detected again, at least on one sample, the control and subsequent batches of products are subjected to continuous control (sorting). With a positive result of continuous control, they return to the established procedure for acceptance tests. 6.6 Periodic tests according to the performance indicators specified in 5.3.1 - 5.3.7 are carried out when they are put into production or when changes are made to the design of products or their manufacturing technology, but at least once in the period specified in Table 8, and also when product certification. In justified cases, it is allowed to combine periodic and certification tests. Qualification tests of products are carried out for all indicators when putting products into production. Tests are carried out in test centers accredited for the right to conduct them. Tests to determine the reduced resistance to heat transfer, air permeability, sound insulation are subjected to structures designed to withstand these loads according to their field of application. 6.7 The consumer has the right to conduct a quality control check of products, while observing the sampling procedure and test methods specified in this standard. When accepting products by the consumer, a batch is considered to be the number of products shipped for a specific order, but not more than 90 pieces, drawn up with one quality document. 6.8 When accepting products by the consumer, it is recommended to use the one-stage quality control plan for products given in Table 9. Table 9

Note - Significant and critical defects include: defects leading to loss of performance, unrecoverable without replacing a part of the product (breakage of a steel profile, etc.), exceeding the maximum deviations of dimensions by more than 1.5 times established in the RD, disassembly of products. Minor defects include removable defects: minor surface damage, unadjusted door fittings and hinges, exceeding the limit deviations of dimensions by less than 1.5 times established in the ND. By agreement of the parties, acceptance of products by the consumer can be carried out at the manufacturer's warehouse, at the consumer's warehouse or in another place specified in the supply contract. 6.9 Each batch of products must be accompanied by a quality document (passport). An example of filling out a product passport is given in Appendix D. 6.10 Acceptance of products by the consumer does not relieve the manufacturer from liability in case of detection of hidden defects that led to a violation of the product performance during the warranty period.

7 Control methods

7.1 Methods of incoming and production operational quality control are established in the technological documentation. 7.2 Methods for quality control of products during acceptance control and acceptance tests 7.2.1 The geometric dimensions of products, as well as the straightness of the edges, are determined using the methods established in GOST 26433.0 and GOST 26433.1. Limit deviations from the nominal dimensions of product elements, the difference in the lengths of the diagonals and other dimensions are determined using a metal measuring tape according to GOST 7502, a caliper according to GOST 166, and probes according to ND. The maximum deviations from the straightness of the edges are determined by applying a calibration ruler in accordance with GOST 8026 or a building level with a flatness tolerance of at least the 9th degree of accuracy in accordance with GOST 9416 to the tested part and measuring the largest gap using probes according to ND. 7.2.2 Limit deviations from the nominal dimensions of the gaps under the overlay are checked using a set of probes or a ruler in accordance with GOST 427. mating surface to the bottom surface. 7.2.4 Appearance, quality of welds, color and quality of finishing of products are evaluated visually by comparison with standard samples approved in the prescribed manner. Surface defects visible to the naked eye from a distance of 1.5 m in natural light of at least 300 lux are not allowed. 7.2.5 Adhesion (strength of adhesion of paint and varnish coatings to the metal surface) is determined by the method of lattice cuts according to GOST 15140. packaging is checked visually. To determine the tightness of sealing gaskets, compare the dimensions of the gaps in the porches and the degree of compression of the gaskets, which should be at least 1/5 of the height of the uncompressed gasket. Measurements are made with a caliper or a ruler in accordance with GOST 427. The tightness of sealing gaskets with closed canvases can be determined by the presence of a continuous trace left by a coloring matter (for example, colored chalk), previously applied to the surface of the gaskets and easily removed after inspection. 7.2.7 The operation of the door hinges is checked by opening and closing the leaf elements of the product ten times. In case of detection of deviations in the operation of door devices, they are adjusted and re-checked.

7.3 Methods of control during periodic tests 7.3.1 The reduced resistance to heat transfer is determined according to GOST 26602.1. 7.3.2 Air and water permeability is determined according to GOST 26602.2. 7.3.3 Sound insulation is determined according to GOST 26602.3. 7.3.4 Indicators of reliability, resistance to static, dynamic, impact loads are determined according to RD and methods approved in the prescribed manner. When testing for dynamic load resistance, they simulate the load that occurs when the door leaf is suddenly opened (for example, during a draft), at the moment the door leaf contacts the slope of the doorway. The test for resistance to impact with a soft inelastic body is carried out with a three-time impact, for example, a pear with a lower diameter of (300 ± 5) mm and a mass of (30 ± 0.5) kg, from a height of fall according to 5.3.5 into the central zone of the sample. Note - At the end of the test, the door blocks must remain operational, while the bolt of the lock and the latch must freely enter their mating parts. Before and after testing the door units for failure-free operation, it is recommended to check the tightness of the seals in accordance with 7.2.6. When testing door blocks for resistance to a static load acting perpendicular to the plane of the door leaf in the free corner zone, it is recommended to use the graph of dependence of the deflection of the free corner of the door leaf on the applied load given in Appendix D. 7.3.5 Quality control methods for welded joints (5.3. 10) are installed in the manufacturer's technical documentation in accordance with GOST 5264.

8 Packaging, transport and storage

8.1 Packaging of products must ensure their safety during storage, handling and transportation. 8.2 Devices or parts of devices that are not installed on the products must be packed in polyethylene film in accordance with GOST 10354 or in other packaging material that ensures their safety, tightly tied and delivered complete with products. 8.3 Opening webs of products before packaging and transportation must be closed on all locking devices. 8.4 Products are transported by all means of transport in accordance with the rules for the carriage of goods in force for this type of transport. 8.5 During storage and transportation of products, they must be protected from mechanical damage and exposure to precipitation. 8.6 When storing and transporting products, it is recommended to install gaskets made of elastic materials between products. 8.7 Products are stored in a vertical or horizontal position on wooden linings, pallets or in special containers in covered areas. 8.8 Warranty period of storage of products - 1 year from the date of shipment of products by the manufacturer.

9 Manufacturer's warranties

9.1 The manufacturer guarantees the compliance of products with the requirements of this standard, provided that the consumer complies with the rules for transportation, storage, installation, operation, as well as the scope established in the regulatory and project documentation. 9.2 In agreement with the consumer (customer), the manufacturer provides service, including emergency opening of doors in case of loss or breakage of keys, advice on the use and operation of door devices and locking mechanisms, and repair of products. 9.3 The warranty period for door blocks is set in the supply contract, but not less than three years from the date of shipment of the products by the manufacturer.

Annex A

(mandatory)

Terms and Definitions

For the purposes of this International Standard, the following terms apply with their respective definitions. door: An element of a wall structure intended for entry (exit) into the internal premises of buildings (structures) or for passage from one room to another and consisting of a doorway, a door block, a sealing system for mounting joints and fasteners and cladding. doorway: An opening in the wall for the installation of a door unit and installation of a mounting seal. door block: A structure generally consisting of a box (frame) rigidly fixed in the doorway, with a leaf hung on hinges with locking devices, which, when the leaf is closed, protects the premises from climatic, noise (and other) influences, as well as unauthorized passage. The door unit may include a number of additional elements: a closer, an opening angle limiter, a peephole, etc. box: An assembly unit of the door unit designed for hanging the door leaf (s), fixedly fixed to the slopes of the doorway. leaf: The assembly unit of a door block connected to the frame by means of movable links (usually hinges). inner sheet: A sheet of fabric located on the side of the guarded or protected premises or object. profile: The profile detail of the box or strapping (frame) of the canvas. porch: The junction (connection node) of the web to the frame profiles. surfacing: A protrusion of the profile of the web (box), covering the gap in the porch and intended, as a rule, to press the gaskets. right (left) opening door block: A door block with hinges located on the right (left) side when viewed from the leaf opening side. Note - In a double-leaf door block, the right or left opening is determined by the location of the door leaf, which opens first (Figure A.1).

a - right opening door block; b - left opening door block; c - right opening door block with horizontal and vertical leaf inserts

Figure A.1 - Definition of products in the direction of opening of the canvases

horizontal (vertical) leaf-insert: A non-opening leaf installed above or next to the opening leaf (Figure A.1, c). locking devices: Devices designed to fix door leaves in the closed position (locks, latches, etc.). reinforcing profile: A profile installed inside the door leaf to provide the necessary rigidity and structural strength. hatch: A metal sheet installed on mechanical links on the inside of the leaf at the place where the lock is attached, providing access to the lock if it needs to be repaired. anti-removable passive crossbars (pins): Reinforcing crossbars connecting the closed leaf with the frame, installed on the vertical profile of the door leaf from the hinge side (or on the vertical profile of the frame from the hinge side) and providing additional resistance to burglary of the door unit. mounting "lugs": Metal mounting plates, as a rule, welded to the profiles of the box (frame), providing the possibility of fastening the door unit in the wall opening.

The characteristics of the door blocks given in Table B.1 are set in the working design documentation and (or) the technical documentation of the manufacturer. Test methods - according to the methods approved in the prescribed manner. Tests are carried out in testing laboratories accredited for the right to conduct such tests.

General requirements for the installation of products

E.1 The requirements for the installation of products are established in the design documentation for construction sites, taking into account the design options adopted in the project for the junctions of products adjoining walls, designed for specified climatic and other loads. E.2 Installation of products must be carried out by specialized construction companies or specially trained teams of the manufacturer. Completion of installation work must be confirmed by an acceptance certificate, which includes the manufacturer's warranty obligations. E.3 At the request of the consumer (customer), the manufacturer (supplier) of products must provide him with a standard instruction for the installation of door blocks, approved by the head of the manufacturer and containing: drawings (diagrams) of typical mounting junctions; list of materials used (taking into account their compatibility and temperature conditions applications); the sequence of technological operations for the installation of door blocks. E.4 When designing and executing junction nodes, the following conditions must be met: sealing of mounting gaps between products and slopes of openings of wall structures must be tight, tight around the entire perimeter of the door block, designed to withstand climatic loads outside and operating conditions inside the premises; the design of the junctions of external products (including the location of the door block along the depth of the opening) should prevent the formation of cold bridges (thermal bridges) leading to the formation of condensate on internal surfaces as much as possible doorways; the operational characteristics of the structures of the junction points must meet the requirements established in building codes. A version of the mounting assembly of the internal door unit is shown in Figure E.1.

1 - box (frame) of the door block; 2 - polyurethane foam; 3 - outer seal; 4 - leaf of the door block; 5- inner seal; 6 - decorative frame portal;

7 - casing; 8 - mounting anchor; 9 - mounting ear; 10 - wall

Figure E.1 - Version of the mounting assembly of the internal door unit

E.5 The number and location of the mounting ears, the type, diameter and length of the fasteners are set in the working design documentation, taking into account the material of the walls and the design of the doorway. It is recommended to use building anchors with a diameter of at least 10 mm as fasteners for the installation of products. The distance between fasteners is at least 700 mm. It is not allowed to use sealants, adhesives, foam insulation, as well as building nails for fastening products. E.6 Door blocks should be installed according to the level and plumb. The deviation from the vertical and horizontal profiles of boxes of mounted products should not exceed 1.5 mm per 1 m of length, but not more than 3 mm for the height of the product. At the same time, if the opposite profiles are deflected in different directions (“twisting” of the box), their total deviation from the normal should not exceed 3 mm. The door block is installed in the prepared doorway symmetrically with respect to the central vertical of the opening. The deviation from symmetry should not exceed 3 mm in the direction of the slope of the opening, intended for fastening the profile of the box with hinges. Deviation from symmetry to the other side of the opening is not recommended. E.7 To fill mounting gaps (seams) of external products, mounting foam, silicone sealants, pre-compressed PSUL sealing tapes (compression tapes), insulating polyurethane foam cords, foam heaters, mineral wool and other materials that have a hygienic conclusion and provide the required performance of the seams are used . Painting seams is not recommended. E.8 When arranging assembly joints and installing external door blocks, it is recommended to take into account the requirements of GOST 30971.

The subject of the material presented by us below was GOST for steel doors equipped with locking devices and installed in industrial and civil buildings. The only thing that this standard does not cover is doors, which are subject to special requirements: resistance to aggressive substances, explosion resistance, bulletproofness and fire safety.

The use of all other products, which the video in this article will also tell about, depends on the conditions of their operation, and is regulated by GOST doors 31173.

Steel doors GOST 31173 2003 are classified according to six main features. First of all, this, of course, is the purpose, as they can be: street, internal and vestibule. And internal doors can be entrance apartment doors, and operated as an ordinary interior door.

Structural differences

The second feature determines the design of the door unit. Here the difference may be in the box, since it is closed; is the shape of the letter "P"; or completed with a threshold, which is an additional element.

  • The next classification feature concerns the number of canvases and options for opening them. The most common doors with one leaf - left or right opening. Next come the canvases of which can be either the same or have different widths.

  • - most often these are ceremonial models, they can also be decorated with inserts. This is either a rectangular or semicircular transom, located horizontally above the opening, or narrow non-opening canvases on the sides of the canvas. This is exactly what we see in the photo above.

Doors are also distinguished by the direction in which they open: outward or inward. It also matters how many sealing circuits are located in the porch. There are usually two of them, but there may be more.

Facing options and performance

The fourth sign by which steel doors GOST 31173 2003 are classified is their front finish.

There are seven options here:

  • Number one is paint.- both traditional and powdered. These are the most popular finishes (see): in the first case, the main criterion for choosing products by the consumer is a low price, and in the second, the incredible strength of the coating, which has already been called anti-vandal.
  • Next come the options with natural or artificial leather lining and insulation; decoration with film coatings; facing with wood roll or board materials (veneer, MDF lining). By the way, many of these types of finishes can be done on old or do-it-yourself doors.

Note! For all types of polymer coatings used for decorating doors, the manufacturer must provide a conclusion confirming their sanitary safety.

  • Glass or mirror finishes look very nice on the doors, especially the front doors.. Alternatively, the canvas is ennobled with a metal overlay with beautiful milling or engraving, or several finishing methods are combined in one model. In general, having coordinated its actions with the customer, the manufacturer can perform any other type of decor - even gilding.

With regard to thermal properties, according to GOST, steel exterior doors are divided into three classes according to heat transfer resistance. At a minimum, this indicator should be 0.4 m2 * C / W.

Anything less is not classifiable. The highest class is with a heat transfer resistance of more than 1 m2 * C / W. There is also a table in the standard, which presents the desired indicators of breathability and water resistance.

Soundproofing for steel doors is of no less importance. There are also three classes, the division of which is carried out according to the level of noise reduction.

Indicators less than 20 decibels are not subject to classification. The third class is the lowest, with indicators up to 25 dB, in the second class up to 31 dB, but the first class is more than 32 dB.

Mechanics and protective qualities of products

The standard for doors made of metal also presents a table with strength indicators, which are also divided into three classes. In total, there are five different characteristics in it, according to the value of which the doors belong to one or another class. It is set according to the worst test result.

This is the resistance to static loads acting in the plane of the web; perpendicular to the canvas; and in the loop area. It also regulates the level of resistance to dynamic impact in the direction where the canvas opens, and to impact in both directions.

By security properties, doors are classified as follows:

  1. Standard doors. They are equipped with locking mechanisms of at least the third class (M3), and anti-removable pins.
  2. Reinforced blocks. Here, reinforced door hinges are added to the above, and locks with a large number of crossbars, which can lock the door around the entire perimeter of the porch. Their strength must correspond to the second class (M2).
  3. Security door blocks. These are all the same reinforced blocks, but the characteristics of the locks installed in them must correspond to the first class of strength (M1).

  • You can also find out whether the doors are reinforced in front of you, or protective, by their marking. The corresponding letter "U" or "Z" is simply added to it. In general, this standard recommends that manufacturers indicate all the data mentioned above in the product passport. They are also encrypted in the marking.

Information should include: design solution; the option of filling the canvas and its front finish; dimensions; lock class. The passport must be accompanied by a scheme for opening the canvas or canvases, as well as instructions for installation and operation of the product.

Requirements for steel doors

Paragraph five of the standard we are discussing, voices a list of requirements that apply to door blocks made of steel. Among the general provisions, information is given that the canvas is a welded structure, for the manufacture of which steel sheets or bent profiles are used.

Welding is a mandatory connection of parts. Other types of joints are permissible only if, in terms of strength characteristics, they are ahead of welded ones - but this, in general, is unlikely. With regards to the design solutions of canvases, the standard presents four main options.

Structural types of canvases

The first option is as follows: the canvas is made on a frame of profiles with a closed hollow section, and two steel sheets are welded to it. In this case, the filling of the canvas is used honeycomb (corrugated cardboard, or hardboard). The second type of metal doors looks like a bent box mounted on profiles with a U-shaped section. Inside, such canvases are filled with polystyrene foam.

  • In the third variant, the leaf frame is welded from profiles of a more complex section, filled with mineral insulation, and closed from the outside with a steel sheet, and from the side of the room with sheet wood material - for example, solid fiberboard. This is the type of door you see in the picture below.

  • The fourth option is also combined: the frame, filled with foam, is made of wooden bars - and only its edges are protected with an angular steel profile. The outer and inner sides, as in the third case, are closed on one side with a steel sheet, and on the other side with a wood-fiber sheet.
  • Regardless of the design option, mullions should be used in the canvases - stiffeners that reinforce the frame of the canvas. They can be not only vertical or horizontal, but also inclined. It is mandatory to reinforce loop zones, as well as places where anti-removable pins are installed.
  • In the manufacture of metal sheets, the standard allows facing the inside not with a solid steel sheet, but with cut blanks welded together along a profile that reinforces the seams. A hatch must be provided on the inner sheet, which is necessary for repairing the lock or latch.

  • Locking mechanisms, which include not only locks and latches, but also latches, are mounted on special linings, screws and threaded clamping brackets. Welding is not used in this case, since in its process it is easy to spoil some parts of the lock.
  • Holes into which the deadbolt or bolt of the lock enters must be protected by a metal box, which is welded into the frame profile. The entry of the deadbolt when closing the lock must be free - and for this, the size of the hole must be at least 2.2 cm larger than the cross section of the deadbolt.
  • The proper level of sound insulation is achieved by installing two sealing contours. Gaskets are mounted around the entire perimeter of the web, avoiding the slightest gap. If the door unit is intended for outdoor installation, then the seals must be resistant to moisture and temperature changes.

It should be noted that there are some restrictions on the doors according to GOST 31173 2003 - namely, their dimensions and weight. The following indicators should not exceed:

  1. height: 2.2m
  2. in width: 1.2m
  3. by canvas area: 9m2
  4. by web weight: 250kg

For doors manufactured in excess of the above standards, additional calculations are made, and their compliance with the requirements of the standard is confirmed by the results of individual tests.

  • In order to remove the canvas closed door it is impossible to make it impossible from the hinges, the design of the product provides for fixed crossbars, or, as they are called, anti-removable pins. They are mounted on the frame of the canvas, and fastened by welding, riveting, or pressing.
  • The size of the pins, their number and location must be indicated in the working drawings. But most often they are provided next to the loops, as this is the most reliable option.

In order for the door frame to be installed in the opening, details are welded to its profile, which are called mounting ears. Other solutions directed by the manufacturer to ensure the strength of the installation of the unit are also allowed.

Dimensions and tolerances

About what should be the maximum dimensions in height and width, it has already been said above. In general, metal doors, like any other, are made in standard versions.

If this is a single-leaf door, then the most running dimensions: for the front door 2.1*0.9m, for the inner door 2.0*0.8m. Although, of course, the options may be different. In any case, both the dimensions and the drawings applied to the canvas are necessarily reflected in the technical documentation of the product.

  • In addition to the dimensions of the door itself, it reflects the sections of the profiles, the detailed dimensions of the nodes and gaps. The drawings indicate the locations of the locking devices, holes for them, and loops. The standard also contains a table that defines the maximum allowable deviations from dimensional intervals.
  • In general terms, 3 mm is the maximum that is allowed only by internal size boxes over 2m high. The minimum is allowed for the outer dimension of the web, which is 1 mm / 1000 mm. In the gaps under the overlay, there should not be a difference of more than 1.5 mm.

  • The manufacturer must control the length of the diagonals, the sag of the front skins, and the straightness of the edges of the frame and canvas with the same care. All geometric parameters are calculated taking into account the design features of the product, the technology of its installation, and in accordance with the standard 21778, which has been in force since 1981.
  • GOST, which is discussed in this article, imposes requirements both on the materials used in production, components and seals, and on finished products. In particular, steel elements must be free of warps, cracks, cavities, dents and rust. Although a slight waviness that does not damage the aesthetics of the product as a whole is allowed.

Delivery of the steel door block is carried out assembled with a locking device. This is mandatory - but such components as a peephole, an opening angle limiter, a door closer are installed by additional agreement of the customer. The product must have a label, or a marker inscription, informing which manufacturer, when, and for what order it was manufactured. Also, the block must be marked and stamped by the department that carried out the technical control.

STEEL DOOR BLOCKS

Specifications

INTERSTATE SCIENTIFIC AND TECHNICAL COMMISSION
ON STANDARDIZATION, TECHNICAL REGULATION
AND CERTIFICATIONS IN CONSTRUCTION (MNTKS)

Moscow

Foreword

The Eurasian Council for Standardization, Metrology and Certification (EASC) is a regional association of national standardization bodies of the states that are members of the Commonwealth of Independent States. In the future, it is possible that national bodies for standardization of other states will join the EASC

The Interstate Scientific and Technical Commission for Standardization, Technical Regulation and Certification in Construction (MNTKS) operates under the EASC, which has the right to adopt interstate standards in the field of construction

The goals, basic principles and basic procedure for carrying out work on interstate standardization are established by GOST 1.0-92 “Interstate standardization system. Basic Provisions” and MSN 1.01-01-96 “System of Interstate Regulatory Documents in Construction. Basic Provisions»

About the standard

1 DEVELOPED by the Center for Certification of Window and Door Equipment and the Federal State Unitary Enterprise Central Design and Technological Bureau (FSUE TsPKTB of the Gosstroy of Russia) with the participation of the Academy of Security and Law and Abloy Oy, Bjerkboda Plant, Finland

2 INTRODUCED by Gosstroy of Russia

3 ADOPTED by the Interstate Scientific and Technical Commission for Standardization, Technical Regulation and Certification in Construction (ISTCS) on May 14, 2003

Short name of the country according to MK (ISO 3166) 004-97

Country code according to MK (ISO 3166) 004-97

Abbreviated name of the state construction management body

Ministry of Urban Development of the Republic of Armenia

Kazakhstan

Kazstroykomitet of the Republic of Kazakhstan

Kyrgyzstan

State Commission for Architecture and Construction under the Government of the Kyrgyz Republic

Ministry of Ecology, Construction and Territorial Development of the Republic of Moldova

the Russian Federation

Gosstroy of Russia

Tajikistan

Komarchstroy of the Republic of Tajikistan

Uzbekistan

Gosarchitektstroy of the Republic of Uzbekistan

4 INTRODUCED FOR THE FIRST TIME

5 Entered into force on March 1, 2004 as the state standard of the Russian Federation by the Decree of the Gosstroy of Russia dated June 20, 2003 No. 76

Information about the entry into force (termination) of this standard and changes to it in the territory of the above states is published in the indexes of national (state) standards published in these states.

Information about changes to this standard is published in the index (catalog) "Interstate standards", and the text of the changes - in the information indexes "Interstate standards". In case of revision or cancellation of this standard, the relevant information will be published in the information index "Interstate Standards".

INTERSTATE STANDARD

STEEL DOOR BLOCKS

Technicalconditions

Steel doors Specifications

Date of introduction - 2004-03-01

1 area of ​​use

This standard applies to steel door blocks with installed locking devices (hereinafter referred to as door blocks or products) for buildings and structures for various purposes.

The standard does not apply to door blocks for special purposes in terms of additional requirements for fire safety, explosion and bullet resistance, exposure to aggressive environments, etc., as well as to door blocks of protective cabins according to the current regulatory documentation.

The scope of specific types of products is established depending on the operating conditions in accordance with the current building codes and regulations, taking into account the requirements of this standard.

The standard can be applied for certification purposes.

2 Normative references

This document makes reference to the following standards:

1 - upper locking crossbar; 2 - upper link of the main lock; 3 - web frame (welded steel profiles); 4 - places for attaching the internal "hatch"; 5 - valve; 6 - the place of attachment of the upper link; 7 - crossbar of the deadbolt of the lever lock; 8 - latch; 9 - deadbolt of the cylinder lock; 10 - lower link of the main lock; 11 - places for fastening the finish; 12 - internal cavity for filler; 13 - vertical thrust guide; 14 - lower locking crossbar; 15 - mounting "eye"; 16 - threshold; 17 - hole for anti-removable crossbar (pin); 18 - anti-removable passive crossbar (pin); 19 - mounting anchor; 20 - box (frame); 21 - combined lever-cylinder lock; 22 - inner steel sheet; 23 - outer steel sheet; 24 - loop knot; 25 - peephole

Picture 1 - An example of the design of a door unit, the leaf of which is welded from two steel sheets and steel profiles, the frame (frame) is made of a bent steel profile

Door leaf with two steel sheets, steel box profiles and honeycomb core

Door leaf with an outer steel sheet and an inner sheet of fiberboard, with profiles of complex cross-section and filling with wood or mineral insulation


Door leaf of "bent box" type, with U-shaped steel profiles and foam filling


Door leaf with steel outer sheet and fiberboard inner sheet, steel angle profiles with timber bars and foam core

Figure 2 - Examples of door leaf designs

Figure 3 - An example of the design of a door block welded from steel sheets and profiles (with filling the middle profile of the frame and door leaf with wood and foam material)


Figure 4 - An example of the construction of a door block welded from steel sheets and profiles, with natural wood cladding

Figure 5 - An example of the design of a double-leaf door block with a lining of wood or wood-based materials (horizontal section)

Figure 6 - Examples of door leaf designs welded from two flat steel sheets and steel profiles (a) and a bent box type door leaf (b) with vertical reinforcing profiles



5.4 Requirements for materials and components (including gaskets)

5.4.1 Materials and components used for the manufacture of door blocks must comply with the requirements of standards, specifications, technical certificates approved in the prescribed manner.

5.4.2 Materials and components used for the manufacture of door blocks must be resistant to climatic influences.

5.4.3 The surfaces of steel elements of boxes and sheets should not have cracks, mechanical damage, pits, distortions, rust. On the front surfaces of steel elements, slight local depressions, risks, waviness up to 0.5 mm deep are allowed, which do not reduce the functional properties and quality of products.

5.4.4 Steel parts of structures should be made of steel grades that ensure the strength characteristics of structural elements, welded, bolted and other connections, depending on the nature and conditions of their work.

Steel elements are recommended to be made from steel grade not lower than StZkp2 according to GOST 380, rolled section according to GOST 1050 or high-alloy steel according to GOST 5632.

5.4.5 Sealing gaskets must be made of weather- and frost-resistant elastic polymer materials in accordance with GOST 30778.

The fit of the sealing gaskets must be tight, preventing the penetration of water. Sealing gaskets must be installed continuously around the entire perimeter of the porch.

5.4.6 Glued wooden cladding panels must meet the requirements of GOST 30972, profile molded wooden parts - GOST 8242.

5.5 Requirements for hinges, locks and other locking devices

5.5.1 In the manufacture of products, locking and auxiliary devices and hinges are used, specially designed for use in metal door blocks. Examples of designs of hinges and locks are given in the appendix.

The type, number, location and method of fastening of locking devices and hinges are set in the working documentation based on the size and weight of the opening elements of the product, as well as the operating conditions of the door blocks. Cloths of door blocks weighing more than 200 kg, as well as products used in public buildings (schools, hospitals, etc.), are recommended to be hung on three hinges. The recommended location of the middle hinge is 150 - 200 mm below the top one.

5.5.2 For hanging canvases on a box (frame), it is recommended to use overhead bearing or other hinges with the ability to adjust in different planes.

5.5.3 Locks not lower than class III according to GOST 5089 . Locks must comply with the requirements of GOST 538 and GOST 5089 .

To improve the protective properties of door blocks, it is recommended to use multi-bolt locks with locking along the perimeter of the door block or locks with rods with additional locking in the upper and lower horizontal frame profiles.

To avoid clogging of the hole for the lower vertical bolt included in the bottom profile of the box, it is recommended to use deviators.

5.5.4 Depending on the purpose of the door blocks in the project documentation, as well as when placing orders, it is necessary to provide for the complete set of products with latches, door closers (closers), opening angle limiters (stops), eyes, chains, etc.

Once every two years

Reliability

Ergonomic Compliance

Reduced resistance heat transfer

Once every five years

Breathability

Soundproofing

* Test type I - acceptance tests during acceptance control; test type II - acceptance tests conducted by the quality service of the manufacturer; test type III - periodic tests carried out in independent test centers.

** Controlled nominal dimensions for test type II are set in the technological documentation.

6.5 Each batch of products undergoes control acceptance tests conducted by the quality service of the manufacturer. The list of controlled indicators and the frequency of control are given in the table.

For testing from a batch of products by random selection, samples of door blocks are taken in the amount of 3% of the batch volume, but not less than 3 pcs. If there are less than 3 products in a batch, each product is subjected to control.

In the event of a negative test result for at least one indicator on at least one sample, a re-check of the quality of products is carried out on a double number of samples for the indicator that had a negative test result.

If a discrepancy between the indicator and the established requirements is detected again, at least on one sample, the control and subsequent batches of products are subjected to continuous control (sorting). With a positive result of continuous control, they return to the established procedure for acceptance tests.

6.6 Periodic tests according to the performance indicators specified in - are carried out when putting into production or when making changes to the design of products or the technology of their manufacture, but at least once in the period specified in the table, as well as during product certification. In justified cases, it is allowed to combine periodic and certification tests.

Qualification tests of products are carried out for all indicators when putting products into production.

Tests are carried out in test centers accredited for the right to conduct them.

Tests to determine the reduced resistance to heat transfer, air permeability, sound insulation are subjected to structures designed to withstand these loads according to their field of application.

6.7 The consumer has the right to conduct a quality control check of products, while observing the sampling procedure and test methods specified in this standard.

When accepting products by the consumer, a batch is considered to be the number of products shipped for a specific order, but not more than 90 pieces, drawn up with one quality document.

Limit deviations from the nominal dimensions of product elements, the difference in the lengths of the diagonals and other dimensions are determined using a metal measuring tape according to GOST 7502, calipers according to GOST 166, probes according to ND.

The maximum deviations from the straightness of the edges are determined by applying a calibration ruler in accordance with GOST 8026 or a building level with a flatness tolerance of at least the 9th degree of accuracy in accordance with GOST 9416 to the tested part and measuring the largest gap using probes according to ND.

7.2.2 Limit deviations from the nominal dimensions of the gaps under the overlay are checked using a set of probes or a ruler in accordance with GOST 427.

7.2.3 The sag in the mating of adjacent parts lying in the same plane is determined with a probe as the distance from the edge of the ruler according to GOST 427, applied to the upper mating surface, to the lower surface.

7.2.4 Appearance, quality of welds, color and quality of finishing of products are evaluated visually by comparison with standard samples approved in the prescribed manner. Surface defects visible to the naked eye from a distance of 1.5 m in natural light of at least 300 lux are not allowed.

7.2.5 Adhesion (strength of adhesion of paint and varnish coatings to the metal surface) is determined by the method of lattice cuts according to GOST 15140 .

8 Packaging, transport and storage

8.1 Packaging of products must ensure their safety during storage, handling and transportation.

8.2 Devices or parts of devices that are not installed on the products must be packed in polyethylene film in accordance with GOST 10354 or in other packaging material that ensures their safety, tightly tied and delivered complete with products.

8.3 Opening webs of products before packaging and transportation must be closed on all locking devices.

8.4 Products are transported by all means of transport in accordance with the rules for the carriage of goods in force for this type of transport.

8.5 During storage and transportation of products, they must be protected from mechanical damage and exposure to precipitation.

8.6 When storing and transporting products, it is recommended to install gaskets made of elastic materials between products.

8.7 Products are stored in a vertical or horizontal position on wooden linings, pallets or in special containers in covered areas.

8.8 Warranty period of storage of products - 1 year from the date of shipment of products by the manufacturer.

9 Manufacturer's warranties

9.1 The manufacturer guarantees the compliance of products with the requirements of this standard, provided that the consumer complies with the rules for transportation, storage, installation, operation, as well as the scope established in the regulatory and project documentation.

9.2 In agreement with the consumer (customer), the manufacturer provides service, including emergency opening of doors in case of loss or breakage of keys, advice on the use and operation of door devices and locking mechanisms, and repair of products.

9.3 The warranty period for door blocks is set in the supply contract, but not less than three years from the date of shipment of the products by the manufacturer.


a -right opening door block; b - left opening door block; v - right opening door block with horizontal and vertical leaf inserts

(reference)

An example of determining the strength class of a door unit


Figure D.1 -Deflection curve Δf, mm, web free angle from the applied load R, kN, when testing door blocks for resistance to static load acting perpendicular to the leaf plane in the area of ​​the free corner

An example of filling out a door block passport

___________________________________________________

(name of manufacturer)

__________________________________________________________________

(address, phone, fax of the manufacturer)

The passport(quality document)
reinforced outer steel door block according to GOST 31173-2003

a) design - single-floor, right-hand execution, with a threshold, opening inwards;

b) overall dimensions - height 2300 mm, width 970 mm.

Symbol DSN PPVn 3-2-3 M2 U 2300-900-60 GOST 31173-2003

Certificate of conformity ____________________________

(certificate number)

Completeness

a) type of finishing of the canvas - combined (milled MDF board; vinyl artificial leather);

b) door hinges - two overhead bearing hinges;

c) locking devices - a lever lock and a lock with a cylinder mechanism;

d) the number of contours of sealing gaskets - 2 circuits;

e) additional information. The delivery set of the product includes: closer (closing regulator), door stop (opening limiter), operating instructions.

Main technical characteristics confirmed by tests

The reduced resistance to heat transfer is 0.65 m 2 · ° C / W. Air permeability at Δ P0 \u003d 100 Pa - 15 m 3 / (h m 2). Sound insulation - 22 dB.

Reliability, opening - closing cycles - 500,000. Mechanical characteristics class - M 2.

Warranty period - 3 years.

Batch number - 89.

Order number / position in the order - 17/9.

Quality Control Receiver._________________ Date of manufacture "___" ____________200__.

(signature)

Appendix E

General requirements for the installation of products

E.1 The requirements for the installation of products are established in the design documentation for construction sites, taking into account the design options adopted in the project for the junctions of products adjoining walls, designed for specified climatic and other loads.

E.2 Installation of products must be carried out by specialized construction companies or specially trained teams of the manufacturer. Completion of installation work must be confirmed by an acceptance certificate, which includes the manufacturer's warranty obligations.

E.3 At the request of the consumer (customer), the manufacturer (supplier) of products must provide him with standard instructions for the installation of door blocks, approved by the head of the manufacturer and containing:

drawings (diagrams) of standard mounting junctions;

list of materials used (taking into account their compatibility and temperature regimes of application);

the sequence of technological operations for the installation of door blocks.

E.4 In the design and execution of junction nodes, the following conditions must be met:

sealing of mounting gaps between products and slopes of openings of wall structures should be tight, tight around the entire perimeter of the door block, designed to withstand climatic loads from the outside and operating conditions inside the premises;

the design of the junction points of external products (including the location of the door block along the depth of the opening) should prevent the formation of cold bridges (thermal bridges) as much as possible, leading to the formation of condensate on the internal surfaces of doorways;

the operational characteristics of the structures of the junction points must meet the requirements established in building codes.

The version of the mounting assembly of the internal door unit is shown in the figure


1 - box (frame) of the door block; 2 - polyurethane foam; 3 - outer seal; 4 - leaf of the door block; 5 - inner seal; 6 - decorative frame portal; 7 - casing; 8 - mounting anchor; 9 - mounting ear; 10 - wall

Annex G

(reference)

Information about the developers of the standard

This standard has been developed working group specialists composed of:

Vlasova T.V., TsS ODT (head);

Mogutov A.V., NIISF RAASN;

Voronkova L.V., Federal State Unitary Enterprise TsPKTB Gosstroy of Russia;

Shvedov D.N., TsS ODT;

Savchenko I.F., TsS ODT;

Savenkov A.V., ANOO Academy "Security and Law";

Petrov E.V., Association "Derzhava";

G. Engblom, Abloy Oy, Bjerkboda plant, Finland;

Gavrilov V.I., CJSC NPVF "Class";

Naan G.G., LLC BIT "Soyuz";

Vlasov A.A., Metal Geometry LLC;

Teplyakov N.N., Voronin V.M., NPP Modul LLC;

Leibman A.A., Leibman G.A., Le-Grand LLC;

Fatykhov Kh.T., Olenev V.T., Guardian Company;

Hitkov V.Yu., Malovichko V.V., Sonex LLC;

Savic B . C., FGUP CNS;

Shvedov N.V., Gosstroy of Russia.

Keywords: door blocks, door leaf, frame, steel sheet

Fire doors are a necessary element of security in industrial enterprises, in shopping and office centers. They allow you to delay the penetration of an open flame into a room with people. Even with a strong fire, such doors do not deform for at least 30 minutes and do not become an additional source of toxins. They are also installed in private houses and apartments, so that in extreme conditions the owners of the dwelling have a chance to get out of the room or wait for help from firefighters. V high-rise buildings it is the fire door that may be the only chance for salvation. It plays an important role in fire suppression and evacuation of people from the scene.

Basic GOSTs

Requirements for a fire door are indicated in GOST, which indicates the fire resistance limit and other basic characteristics. Compliance with these standards provides protection against the penetration of flame and smoke into the room. To obtain a certificate confirming compliance with the necessary parameters of GOST, it is necessary to conduct laboratory tests. The EIR marking shows the limit of structural integrity, thermal insulation properties and the time until the door ignites.

GOST Name and description Download
GOST R 53307-2009 Building structures. Fire doors and gates. Test method for fire resistance.
GOST 31173-2003 Steel door blocks. Designed for technical metal products.
GOST 31173-2016 Steel door blocks. Specifications.
GOST R 53303-2009 Building structures. Fire doors and gates. Test method for smoke and gas permeability. Designed for doors and gates with EIS marking.
GOST R 53308-2009 Building structures. Translucent enclosing structures and filling openings. Test method for fire resistance.

Federal Law, SNiPs, norms, regulations in the field of fire safety

When designing structures and installing fire doors in them, you should also be familiar with official documents in the field of fire safety. Useful links below.

Document Name Download
Federal Law of July 22, 2008 No. 123-FZ Technical regulation on fire safety requirements.
Federal Law of May 6, 2011 No. 100-FZ About the volunteer fire department.
Decree of the Government of the Russian Federation of December 30, 2011 No. 1225 On licensing activities for the installation, maintenance and repair of fire safety equipment for buildings and structures.
Decree of the Government of the Russian Federation of March 31, 2009 No. 272 On the procedure for conducting calculations for the assessment of fire risk.
Order of the Ministry of Emergency Situations of the Russian Federation of June 30, 2009 No. 382 On approval of the methodology for determining the calculated values ​​of fire risk in buildings, structures and structures of various classes of functional fire hazard.
Decree of the Government of the Russian Federation of April 25, 2012 No. 390 About the fire regime.
PPBO 07-91 Fire safety rules for healthcare facilities.
VPPB 01-04-98 Fire safety rules for enterprises and organizations of the gas industry.
PPBO 85 Fire safety rules in the oil industry.
SP 2.13130.2012 Fire protection systems. Ensuring the fire resistance of objects of protection.
SP 7.13130.2013 Heating, ventilation and air conditioning. fire safety requirements.
SP 12.13130.2009 Definition of categories of premises, buildings and outdoor installations for explosion and fire hazard.
SP 1.13130.2009 Fire protection systems. Escape routes and exits.

Classification of doors by types according to GOSTs

Fire doors are classified into three types:

  • Manufacturing material. They are made from wood, metal and glass. The latter allow you to see the source of ignition and the strength of the fire. Metal doors according to GOST can also be made of steel or aluminum. For each type, there are standards that the design must strictly comply with.
  • Construction type. They are divided into single-sided and double-sided. Single-leaf structures consist of a box and a door leaf that opens only in one direction. In this case, the main requirement is to set the threshold. Double-leaf doors can be either equal or unequal, depending on the width of the leaves. It is important to remember that the leaves of double-leaf doors should open in one direction.
  • Degrees of fire resistance. Products come in three types: 1st, 2nd, 3rd. The fire resistance of doors mainly depends on the thickness and type of the inner insulation layer.

Dimensions according to standards

Dimensions GOST regulates the verification of one standard size of doors for a particular manufacturer. The protocol records the test results and dimensions, tolerance which in height and width should not exceed +10% and -30%. The value is only rounded up to 5 cm up and down to 10 cm.

Permits for installation

Fire doors may only be installed in suitable rooms. Since the main function of such structures is to protect people and property from fire, they are often mounted in rooms with an increased likelihood of fire. In industrial enterprises, these are warehouses, corridors, workshops, basements, attics and technical compartments. If the total area of ​​the technical floor exceeds 300 m2, two fire-resistant structures must be installed, while the size of the doors should not be less than 0.75 * 1.5 m. In office centers, such doors are installed in rooms where important documents are stored.

According to consumers, a metal fire door has the highest degree of fire resistance. GOST obliges to use grades of alloyed steels for manufacturing. Non-toxic refractory materials are used as coatings and heaters. Wooden structures, which were previously impregnated with special solutions that slow down the fire, also have sufficient fire resistance. Modern technologies make it possible to use aluminum profiles with thermal storage fillers and laminated refractory glass for the production of doors.

There is no regulatory document regulating the installation of a fire-resistant door. However, for the installation of a fire-fighting structure, a package of documents is required. It consists of a fire safety certificate, a passport for the door and a license to perform door installation work. You also need a well-established door closer that automatically closes the door. A special non-combustible fire-fighting foam must be used for installation. The metal structure should fit snugly against the box, leaving no gap. To ensure the reliability and durability of the door, the sealing rubber should be slightly compressed. Uniform painting, high-quality glued thermal expansion tape, and an adjusted closer will serve as a guarantee of high wear resistance of the structure.

Fire door operation

Caring for fire doors is no different from servicing a conventional metal structure; it is not regulated by GOST. The operation of both wooden and steel doors must be carried out throughout the specified service life. According to GOST standards, a door that has fulfilled its main protective function during a fire is subject to replacement. After that, the fire-resistant fire door is dismantled and replaced.

Fire doors made in accordance with GOST , are more expensive than conventional doors, but they provide security in case of fire. Even if the fire department does not require the installation of such a door, it costs much more than the additional money spent. This design can save not only property, but also people's lives.

INTERSTATE COUNCIL FOR STANDARDIZATION, METROLOGY AND CERTIFICATION

INTERSTATE COUNCIL FOR STANDARDIZATION, METROLOGY AND CERTIFICATION

INTERSTATE

STANDARD

STEEL DOOR BLOCKS

Specifications

(EN 14351-1:2006+A1:2010, NEQ)

(EN 1191:2012, NEQ)

(EN 1192:1999, NEQ)

Official edition

Form Standards

GOST 31173-2016

Foreword

The goals, basic principles and basic procedure for carrying out work on interstate standardization are established by GOST 1.0-2015 “Interstate standardization system. Basic Provisions” and GOST 1.2-2015 “Interstate Standardization System. Interstate standards. rules and recommendations for interstate standardization. Rules for the development, adoption, updating and cancellation "

About the standard

1 DEVELOPED by a private institution "Window and Door Technology Certification Center". Limited Liability Company "DorKhan 21st century", firm "CISA" (Italy)

2 INTRODUCED by the Technical Committee for Standardization TC 465 "Construction"

3 ADOPTED by the Interstate Council for Standardization, Metrology and Certification (Protocol No. 92-P of October 25, 2016)

4 By order of the Federal Agency for Technical Regulation and Metrology dated November 22, 2016 Ns 1739-st, the interstate standard GOST 31173-2016 entered into force as the national standard of the Russian Federation from July 1, 2017.

5 This standard complies with the technical requirements and test methods of the following European standards:

EN 14351-1:2006+A1:2010 “Windows and doors. Standard products, specifications. Part 1: Windows and external pedestrian doorsets without fire resistance and/or smoke leakage characteristics , NEO):

EN 1191:2012 “Windows and doors. Resistant to re-opening and closing. Test method" ("Windows and doors - Resistance to repeated opening and closing - Test method". NEO):

EN 1192:1999 Doors. Classification of mechanical strength requirements "(" Doors - Classification of strength requirements ". NEQ)

6 INSTEAD OF GOST 31173-2003

GOST 31173-2016

Information about changes to this standard is published in the annual information index "National Standards", and the text of changes and amendments - in the monthly information index "National Standards". In case of revision (replacement) or cancellation of this standard, a corresponding notice will be published in the monthly information index "National Standards". Relevant information, notification and texts are also posted in the public information system - on the official website of the Federal Agency for Luchnic Regulation and Metrology and the Internet ()

© Standarginform, 2016

8 of the Russian Federation, this standard cannot be fully or partially reproduced. replicated and distributed as an official publication without the permission of the Federal Agency for Technical Regulation and Metrology

GOST 31173-2016

1 area of ​​use............................................... ...................one

3 Terms and definitions.................................... 3

4 Classification and symbols .................................................................. ....4

5 Specifications .................................................................. ................7

5.1 Design requirements............................................................... ............7

5.2 Dimensions and limit deviations............................................................... .....9

5.3 Performance characteristics............................................................... ..10

5.4 Requirements for materials, accessories and gaskets .........................................13

5.5 Requirements for locking devices and hinges ..............................................................13

5.6 Finishing requirements............................................................... ...............14

5.7 Completeness and marking ....................................................... .........15

5.8 Rules for installation (assembly) of locks .............................................. .....sixteen

5.9 Malfunction and warranty service of the lock.......................................18

6 Rules for acceptance ............................................... .....................eighteen

7 Methods of control and testing ............................................... ............21

8 Packing, transport and storage............................................................... ....23

9 Manufacturer's Warranty............................................................... ................24

Annex A (informative) An example of determining the strength class of door blocks ............... 25

Appendix B (informative) Examples of door block designs and options

filling door panels .................................................................. 26

Annex B (normative) Methods for determining the resistance to static loads

and schemes for the application of dynamic loads............................................31

GOST 31173-2016

INTERSTATE STANDARD

STEEL DOOR BLOCKS Specifications

steel doors. Specifications

Introduction date - 2017-07-01

1 area of ​​use

This standard applies to door steel blocks with installed locking devices (hereinafter referred to as door blocks) intended for installation in outdoor and internal walls buildings and structures for various purposes. The requirements of this standard can be applied to the entrance door blocks of buildings and apartments equipped with a burglar alarm.

The scope of specific types of products is established depending on the operating conditions in accordance with the building codes and rules in force on the territory of the state party to the agreement that adopted this standard, taking into account the requirements of this standard.

This standard does not apply to door units for special purposes in terms of additional requirements for fire safety, explosion and fire resistance. exposure to aggressive environments, etc., as well as on the door blocks of protective cabins in accordance with current regulatory documents. This International Standard may be applied for certification purposes.

2 Normative references

This standard provides normative references to the following interstate standards:

GOST 2.001-2013 Unified system for design documentation. General provisions GOST 3.1001-2011 Unified system of technological documentation. General provisions GOST 9.032-74 Unified system of protection against corrosion and aging. Paint coatings. Groups. technical requirements and designations

GOST 9.301-86 Unified system of protection against corrosion and aging. Metallic and non-metallic inorganic coatings. General requirements

GOST 9.303-84 Unified system of protection against corrosion and aging. Metallic and non-metallic inorganic coatings. General selection requirements

GOST 9.308-85 Unified system of protection against corrosion and aging. Metallic and non-metallic inorganic coatings. Accelerated Corrosion Test Methods

GOST 9.401-91 Unified system of protection against corrosion and aging. Paint coatings. General requirements and accelerated test methods for resistance to climatic factors GOST 9.402-2004 Unified system of protection against corrosion and aging. Paint coatings. Preparation of metal surfaces for painting GOST 99-96 Rotary cut veneer. Specifications GOST 166-89 (ISO 3599-76) Calipers. Specifications

Official edition

GOST 31173-2016

GOST 380-2005 Carbon steel of ordinary quality. Grades GOST 427-75 Measuring metal rulers. Specifications GOST 538-2014 Lock and hardware products. General specifications GOST 1050-88 Rolled bars, calibrated, with a special surface finish from quality carbon structural steel. General specifications

GOST 2140-81 Visible defects of wood. Classification, terms and definitions. Measurement methods

GOST 2977-82 Sliced ​​veneer. Specifications GOST 4598-86 Wood fiber boards. Specifications GOST 5088-2005 Hinges for window and door units. Specifications GOST 5089-2011 Locks, latches, cylinder mechanisms. Specifications GOST 5264-80 Manual arc welding. Connections are welded. Main types, structural elements and dimensions

GOST 5632-2014 Alloyed stainless steels and alloys corrosion-resistant, heat-resistant and heat-resistant. Stamps

GOST 7016-2013 Products made of wood and wood materials. Surface Roughness Options

GOST 7502-98 Metal measuring tapes. Specifications GOST 8026-92 Calibration rulers. Specifications

GOST 8242-88 Profile parts made of wood and wood materials for construction. Specifications

GOST 9416-83 Building levels. Specifications GOST 10354-82 Polyethylene film. Specifications

GOST 15150-69 Machinery, instruments and other technical products. Versions for different climatic regions. Categories, conditions of operation, storage and transportation in terms of the impact of environmental climatic factors

GOST 19091-2012 Locks, latches, cylinder mechanisms. Test methods GOST 23118-2012 Building steel structures. General specifications GOST 23166-99 Window blocks. General specifications GOST 24866-2014 Glued double-glazed windows. Specifications

GOST 26433.0-85 System for ensuring the accuracy of geometric parameters in construction. Rules for performing measurements. General provisions

GOST 26433.1-89 System for ensuring the accuracy of geometric parameters in construction. Rules for performing measurements. Prefabricated elements

GOST 26602.1-99 Window and door blocks. Methods for determining the resistance to heat transfer

GOST 26602.2-99 Window and door blocks. Methods for determining air and water permeability

GOST 26602.3-2016 Window and door blocks. Method for determining sound insulation GOST 26602.5-2001 Window and door blocks. Methods for determining the resistance to wind load

GOST 30698-2014 Tempered glass. Specifications

GOST 30777-2012 Turning, tilting, tilt-and-turn, sliding devices for window and door balcony blocks. Specifications

GOST 30778-2001 Gaskets sealing from elastomeric materials for window and door blocks. Specifications

GOST 30826-2014 Laminated glass. Specifications

GOST 30970-2014 Door blocks made of PVC profiles. General specifications GOST 30971-2012 Mounting seams of junctions to wall openings. General specifications

GOST 30972-2002 Glued wooden blanks and parts for window and door blocks. Specifications

GOST 31149-2014 (ISO 2409:2013) Paint and varnish materials. Determination of adhesion by the lattice notch method

GOST 31471-2011 Emergency door opening devices for evacuation and emergency exits. Specifications

GOST 31173-2016

Note - When using this standard, it is advisable to check the effect of reference standards in a public information system - on the official website of the Federal Agency for Technical Regulation and Metrology on the Internet or according to the annual information index "National Standards", which was published as of January 1 of the current year, and on issues of the monthly information index "National Standards" for the current year. If the reference standard is replaced (modified), then when using this standard, you should be guided by the replacing (modified) standard. If the reference standard is canceled without replacement, the provision in which the reference to it is given applies to the extent not affecting the reference.

3 Terms and definitions

In this standard, the following terms are used with their respective definitions:

3.1 breaking the door: Actions aimed at breaking the integrity of the door or its structural elements in order to gain partial or full access to the room protected by the door.

3.2 burglary-resistant door: A door that is in a closed (locked) state and is an obstacle to unauthorized entry into the building (room) using physical force or using a certain tool.

3.3 inner sheet: Door leaf sheet located on the inside of the door block, on the side of the guarded or protected premises or object.

3.4 internal door block (including the entrance from the staircase): Door block designed to separate the interior of buildings and pass from one room to another.

3.5 door frame (frame): Assembly unit of the door block, designed for hanging the leaf (cloths), rigidly fixed to the slopes of the doorway.

3.6 door leaf: Assembly unit of the door unit connected to the frame by means of movable links (hinges).

3.7 door block: A structure that includes a box (frame), a door leaf with locking devices.

Note vcha niv - The door unit may include a number of additional elements (door closing device (closer), opening angle limiter, peephole, etc.].

3.8 right (left) opening door block: A door block with hinges located on the right (left) side when viewed from the opening side of the door leaf (Figure 1).

a) Right opening door block 6) Left opening door block c) Right opening door block

with horizontal and vertical inserts

Figure 1 - Definition of the door block in the direction of opening the canvases

3.9 doorway: An opening in the wall intended for mounting a door unit.

3.10 door: An element of a wall structure designed to fill doorways and consisting of a door block, fixing the door block to the opening, assembly seams, a system of seals and cladding, and providing protection from climatic conditions when the door leaf is closed. noise and other impacts, as well as from unauthorized passage.

3.11 double-leaf door unit: A door unit consisting of two or more leaves installed in one door frame.

GOST 31173-2016

Note - In a double-leaf door block, the right or left opening is determined by the location of the door leaf, which opens first (Figure 1).

The main leaf of a double-leaf door leaf is used constantly, the second - if necessary.

3.12 locking devices: Devices designed to fix and lock door panels in the closed position (locks, latches, etc.).

3.13 hatch: A hole closed by a lid installed on mechanical links on the inside of the door leaf at the place where the lock is attached, providing access to the lock in case of need for its repair.

3.14 mounting elements: Metal mounting plates, usually welded to the profiles of the box (frame), providing fastening of the door block in the wall opening.

3.15 surfacing: A protrusion of the profile of the door leaf (frame), covering the gap in the porch and designed to press the gaskets.

3.16 external door unit (including vestibule): A door unit separating the internal climate of the premises from the external one and serving mainly for entry (exit).

3.17 outer leaf: The leaf of the door leaf, located on the outer side of the door block (from the side of the intended attack).

3.18 leaf insert: A non-opening door leaf installed above or next to the opening leaf [see figure 1c)].

3.19 porch: The junction (connection node) of the door leaf to the frame profiles.

3.20 anti-removable passive crossbars (pins): Reinforcing crossbars connecting the closed door leaf with the frame, installed on the vertical profile of the leaf from the hinge side (or on the vertical profile of the frame from the hinge side) and providing additional resistance to breaking of the door block.

3.21 strength of the door block: The ability of the structure to perceive the impact of external forces without destruction.

3.22 profile: profile detail of the box or trim (frame) of the door leaf.

3.23 reinforcing profile: A profile installed inside the door leaf to provide the necessary rigidity and strength of the door block.

4 Classification and conventions

4.1 Door blocks are classified according to the following criteria:

Purpose (at the place of installation);

Structural execution;

operational characteristics;

Mechanical strength;

Protective functions.

4.1.1 By purpose, door blocks are divided into groups:

A - external entrances to buildings and structures:

B - entrance to apartments from staircases;

B - internal, separating heated rooms inside buildings, including public and industrial buildings (offices, offices, hotel rooms), as well as on evacuation routes;

B1 - internal door blocks of auxiliary premises (attics, basements, technical floors, vestibules);

G - external entrances to buildings and entrances to apartments with enhanced protective functions.

Notes

1 Classification by purpose allows the consumer to select a door block within the group depending on the expected operating conditions, specific design requirements and consumer properties. For example, entrance door blocks to buildings can be used as entrances to an apartment.

2 Door units with enhanced security functions can be used as entrances to an apartment or auxiliary premises.

3 It is not allowed to use door blocks of strength class M1 and below as entrances to buildings and apartments.

4.1.2 By design, door blocks are classified:

Box design:

GOST 31173-2016

With closed box.

With U-shaped box.

With a U-shaped box with an additional threshold:

According to the design of the door leaf:

Consisting of at least two sheets of steel (outer and inner) connected by welding.

Combined, consisting of one outer steel sheet and an inner one made of other materials (chipboard, plywood, polymer boards, etc.).

"Sandwich" type, consisting of two rolled steel sheets and a layer of insulation between them:

By the number of canvases (including non-opening ones), direction and type of opening:

Single floor (left and right opening).

Double-field (including with canvases of different widths);

By the method of opening the canvas:

Non-opening canvases (inserts),

With opening inside the room.

Outward opening:

According to the number of sealing circuits in the porch:

With one circuit.

With two or more circuits.

4.1.3 According to performance characteristics (reduced resistance to heat transfer, air * and water permeability, sound insulation), door blocks of groups A, B. D are divided into classes 1. 2.3.

The values ​​of operational characteristics of door blocks of the specified classes are given in Table 1.

Table 1 - Classes of door blocks according to performance

For door blocks of groups A and G (entrance door blocks to buildings from the street), it is allowed to determine the water permeability in accordance with GOST 26602.2.

Notes

1 Door units with reduced heat transfer resistance less than 0.4 m^C/Br, volumetric air permeability more than 27 m^h m 2). sound insulation less than 20 dB are not subject to classification according to the indicated indicators.

2 The given resistance to heat transfer for doors of groups A and B is for reference. If necessary, this indicator is confirmed by calculations or laboratory tests.

3 For door blocks of groups A and D, resistance to wind loads is established according to the normative document 1 ^, in force on the territory of the state party to the agreement that adopted this standard.

4 Door blocks of group B, if used as entrances to apartments, should be classified according to performance in accordance with 4.1.3.

11 In the Russian Federation, pressure changes from 400 to 1800 Pa are accepted according to SP 20.13330.2011 "SNiP 2.01.07-85 Loads and impacts".

GOST 31173-2016

4.1.4 Heat transfer resistance, air permeability and sound insulation for doors of groups A and D. installed in the outer walls of heated buildings must comply with the requirements of the regulatory document 1 "in force on the territory of the state party to the agreement that adopted this standard.

4.1.5 In terms of mechanical strength, door blocks are divided into the following classes: M1. M2. M3. M4. MS.

The mechanical strength classes of door blocks are characterized by the values ​​of the applied static loads given in table 2.

Table 2 - Classes of door blocks for mechanical strength

Load value for a door unit of strength class

1 Static load applied in the plane of the door leaf. N. no less

2 Static load applied in the area of ​​the free corner of the door leaf perpendicular to its plane, N., not less than

3 Static load applied to the hinge area perpendicular to the plane of the door leaf. N. no less

4 Static load applied to the zone of the lock and additional locking devices perpendicular to the plane of the door leaf. N. no less

Notes

1 The strength class of the door unit is set according to the worst result of all types of tests (class MS - the highest),

2 Tests according to indicators 2. E. 4 are carried out on door blocks that open inward, according to indicator 1 - in both directions.

3 An example of determining the strength class for a static load acting perpendicular to the plane of the door leaf in the free corner area is given in Appendix A.

4.1.6 Depending on the presence of protective functions, door blocks are divided into:

For standard door units:

Door blocks with reinforced protective functions.

For door units with enhanced security features, additional requirements for burglary resistance may be imposed.

Note - The symbol for door blocks with enhanced protective functions is supplemented with the index "UZ".

Door blocks of groups A. B. C may include separate options for the protective functions of doors of group G.

4.2 For door blocks, the following designations are accepted:

By appointment:

DSN - external steel door block (group A).

DSVh - steel door block entrance from the staircase (group B),

DSV - internal steel door block (group B).

DSVv - internal steel door block for auxiliary premises (group B1), DSUZ - steel door block with enhanced protective functions (group D):

By design:

Dp - two-field.

On - single field.

"" In the Russian Federation, they are guided by the requirements of SP 50.13330.2011 "SNiL 23-02-2003 Thermal protection of buildings" and SP 51.13330.2011 "SNiP 23-03-2003 Noise protection".

GOST 31173-2016

Prg - with a threshold,

Brg - no threshold.

L - left opening.

Pr - right opening.

Vn - opening inside the room.

H - opening outward.

P2ls - with a canvas of two steel sheets.

Pcomb - combined.

Psp - with a door leaf of the "sandwich" type.

Oh - the usual performance.

UZ - with enhanced protective functions (burglary resistant).

4.3 The structure of the symbol for door blocks is given in 4.4. In the symbol of the door block, except for those indicated in 4.2. it is allowed to include dimensions and additional information about performance and mechanical strength classes (see tables 1 and 2).

Note - The dimensions of the door block are the external dimensions along the perimeter of the box (frame) without taking into account the trim and additional elements.

4.4 The structure of the symbol of the door unit:

An example of a symbol for an outdoor steel door block, group A. single-leaf, right-hand opening, with a threshold, outward opening, with a door leaf made of two steel sheets, strength class M3, standard version:

DSN. A. On. Etc. Prg. N. P2ps. M3. O - GOST 31173-2016

Note - For export-import deliveries, as well as in accordance with the order, it is allowed to use a different structure of the symbol. The given structure of the symbol is adopted in accordance with GOST 23166. GOST 24866. GOST 30970, etc.

4.5 When placing an order for manufacturing (delivery) and a passport, it is recommended to indicate: design variant, including a description of the filling of the door leaf: a scheme for opening the leaf and the design of the door unit; type and brand of door devices and class of locks: type of finish, width of the box and other requirements as agreed between the manufacturer and the customer.

5 Technical requirements

5.1 Design requirements

5.1.1 Products must comply with the requirements of this standard, standard sample and be manufactured according to the design and technological documentation of the manufacturer.

Design documentation must comply with the requirements of GOST 2.001. technological documentation - the requirements of GOST 3.1001.

5.1.2 The design of door panels is taken according to 4.1.2.

Note - Door leafs of the "sandwich" type are recommended for use in door blocks without imposing requirements for shaft resistance.

Examples of door block designs and options for filling door panels are given in Appendix B.

GOST 31173-2016

The thickness of the outer sheet of the door leaf is set depending on functional purpose door block, strength class according to table 2 and confirmed by test results. The recommended sheet thickness for door blocks of groups A. B is at least 1.5 mm. group B - not less than 0.S mm. for group D - not less than 1.8 mm. The thickness of the sandwich door leaf must be at least 0.45 mm.

5.1.4 For 8 door leaf designs, it is recommended to use at least two vertical and horizontal reinforcing profiles (multipliers). Reinforcing profiles are allowed to be placed at an angle between the vertical ones (inclined profiles). Horizontal reinforcing profiles are recommended to be placed in the loop zone or in the zone of anti-removal devices. In the designs of "sandwich" type canvases, it is recommended to use L-shaped amplifiers in the loop and lock zones.

5.1.5 In the construction of door panels, it is allowed to use joined sheet blanks welded along reinforcing profiles instead of an internal solid steel sheet. The places of welding points are set in the design documentation.

As an inner sheet, it is allowed to use solid fiber boards in accordance with GOST 4598 or other hard sheet materials that provide sufficient strength.

5.1.6 For the repair of locks and latches at the place of their installation, it is recommended to provide a hatch in the inner sheet, which is fixed on mechanical links.

5.1.7 Locking devices (locks, latches, additional bolts) are recommended to be fixed on screws through special pads and clamping brackets with threaded threads. The fastening of the locking devices must be strong, reliable, excluding their spontaneous displacement during operation and ensuring the requirements for maintainability.

5.1.8 In the structures of external entrances to buildings and internal entrances to the apartment door blocks, in order to increase sound insulation and resistance to heat transfer, it is recommended to install at least two contours of sealing gaskets that provide gaps between the door frame and the leaf.

Sealing gaskets must comply with GOST 30778 and be installed around the entire perimeter of the porch. Sealing gaskets for external door units must be resistant to climatic and atmospheric influences and tested for durability in testing centers accredited to carry out such tests.

5.1.9 The total area of ​​the door unit should not exceed 9 m 2, while the height of the opening door panels is recommended not to exceed 2200 mm. width - no more than 1200 mm for a single-leaf door and no more than 1800 mm for a double-leaf door.

It is allowed to use non-opening horizontal and vertical canvas-inserts.

In the manufacture of door blocks with canvases with an area, weight and dimensions exceeding the specified values, their quality must be confirmed by the results of laboratory tests or additional strength calculations in accordance with the building codes and rules in force on the territory of the state party to the agreement that adopted this standard.

Note - The largest dimensions of the leafs of door blocks of specific types, depending on the mass of the leaf, the moments of section modulus of the profiles of the frame of the leaf, the rigidity of the section of the middle part of the leaf (including the outer and inner lining, filling, reinforcing profit), the location and types of hinges and locking devices should be given in the design documentation of the manufacturer.

In the construction of door frames, the use of vertical posts (sidewalls) and upper lintels (transoms) increased in width is allowed. Sidewalls and transoms can be made both integral with the door frame, and in the form of separate assembly units connected to the door frame during the installation of the door block and the wall opening.

5.1.10 The location and dimensions of the holes for installing locks and other locking devices are set in the design documentation, taking into account the requirements of GOST 5089.

5.1.11 It is recommended to protect the places of holes intended for the bolt entry with special metal or other equal-strength boxes. The box is connected to the profile of the box (frame) as follows. so that they do not interfere with the normal movement of the deadbolt bolts. It is allowed to make holes for the entrance of the deadbolt in the door frame, while the dimensions of the hole must be 2-3 mm larger than the corresponding cross-sectional dimensions of the deadbolt.

Note - Instead of separate holes for the entrance of the bolt, it is allowed to use a single bolt groove. at the same time, the design of the groove should not reduce the strength of the hinge post of the door frame. in the groove

GOST 31173-2016

there may be a device that provides the ability to adjust the location of the door leaf relative to the door frame.

5.1.12 In the design of door blocks on the hinge side, it is recommended to provide anti-removable passive crossbars (pins). The pins must be firmly installed in the frame of the door leaf or in the frame by welding, pressing or riveting. It is allowed to use other types of fastening of anti-removable pins that do not reduce their strength properties. The size, number and location of the anti-detachable pins are set in the working documentation, while it is recommended to install the anti-detachable pins in the loop zone to ensure the greatest protection. Instead of pins, it is allowed to use a single anti-burglary labyrinth, in which the protrusion of the end of the door leaf enters the groove of the hinge post of the door frame along the entire vertical of the door block.

5.1.13 Installation of a door unit in a wall opening is recommended to be carried out using special fastening elements (for example, mounting "lugs"), their number and location are indicated in the design documentation. The fastening elements used must provide the necessary fastening strength and safety during door operation.

5.1.14 It is recommended to use environmentally friendly heat and sound insulating materials as the internal filling of door panels: mineral wool (including basalt) slabs or other materials according to regulatory documents for their manufacture. Filling should fit tightly, without voids, while maintaining density during the life of the door unit.

Note - The density of mineral wool and basalt slabs must be at least 110 kg/m*.

5.1.15 Polymeric and synthetic materials used for filling and finishing door panels must have conclusions on sanitary and fire safety provided for by applicable law and executed in the prescribed manner. Paints used for finishing should not contain lead.

5.1.16 Door blocks must be safe in operation. The safety conditions for the use of door blocks of various designs are established in the design documentation.

Products must be designed for operational loads in accordance with the building feed and rules in force in the territory of the state party to the agreement that adopted this standard. When designing and manufacturing products, calculation programs or calculation methods for determining the strength characteristics of products should be used.

5.1.17 To ensure the normal functioning of the external entrance door blocks of groups A and D to exclude the effects of temperature fluctuations, it is recommended to provide a vestibule in front of the external entrance door.

5.1.18 To ensure barrier-free passage for people with disabilities, group A door units should be equipped with special door closing devices (closers) with a delayed closing system or automatic action with a manual control panel that meet the requirements of regulatory documents 1 'in force on the territory of the state party to the agreement which has adopted this standard.

5.1.19 If there is a threshold in the design of the door unit, its recommended height should be no more than 20 mm.

5.1.20 Door blocks installed on escape routes can be single- and double-leaf, hinged with mandatory opening during evacuation.

For the unhindered leaving of buildings and premises, door blocks must be equipped with emergency door opening devices "Antipanika" in accordance with GOST 31471. It is not recommended to complete door blocks for escape routes with thresholds.

5.2 Dimensions and tolerances

5.2.1 The nominal overall dimensions of the door blocks are set in the design and technical documentation (order, supply contract) for the manufacture of products. Nominal dimensions

1> In the Russian Federation - according to GOST R 56177-2014 “Door closing devices (door closers). Specifications".

GOST 31173-2016

details of product assemblies, sections of profiles and gaps, the dimensions of the location of locking devices, hinges and holes are set in the design documentation for their manufacture.

5.2.2 Limit deviations of the nominal overall dimensions of door blocks should not exceed ± 3.0 mm.

5.2.3 Limit deviations of the nominal dimensions of door blocks, sections of profiles and gaps, dimensions of the location of locking devices, hinges and holes should not exceed the values ​​given in Table 3.

The difference in the lengths of the diagonals of rectangular door panels with an area of ​​1.5 m 2 or less should not exceed 2.0 mm. area over 1.5 m 2 - 3.0 mm.

Table 3 - Limit deviations of nominal dimensions

In millimeters

Note - The values ​​of the maximum deviations of the dimensions of the gaps under the overlay are given for closed canvases with installed sealing gaskets.

5.2.4 The difference in front surfaces (sag) in welded fillet joints shall not exceed* 2.0 mm.

5.2.5 The sagging of the door panels in the assembled door block with a threshold should not exceed

2.0 mm per 1 m width.

5.2.6 The deviation from straightness of the edges of door panels and frames should not exceed

1.0 mm per 1.0 m length.

NOTE The flatness of the door panels is controlled by measuring the distance from points on the surface of the panels to an adjacent horizontal surface.

5.2.7 Nominal diameters of holes for bolted connections and maximum deviations from them. established depending on the method of formation and the type of bolted connection, are accepted according to GOST 23118.

5.3 Performance characteristics

5.3.1 Operational characteristics of door units are given in Table 4.

Table 4 - Operational characteristics of door units

GOST 31173-2016

End of table 4

Characteristic name

Meaning

Door block group

For internal door blocks, including offices, cabinets, hotel rooms, etc.;

For door blocks of entrances to apartments from staircases:

For external entrance door blocks and reinforced entrances to buildings

Notes

1 The need to apply performance characteristics marked with a "k"

", installed in

design and technical documentation, based on the purpose of the door block.

2 Reliability is set taking into account the intensity of passage during operation:

Doors of groups A and D - high level of passage intensity:

Doors of group B (entrance to apartments) - average level of passage intensity:

Doors of group B (doors of internal premises of public and industrial buildings) - medium

intensity level:

Doors of group B1 (internal doors of auxiliary rooms, evacuation and emergency exits)

dov) - low level of passage intensity.

5.3.2 It is recommended to establish the operational characteristics of door blocks for a specific purpose in the design documentation for the construction (reconstruction) of the building and confirm the results of tests at test centers accredited for their right to conduct them.

5.3.3 Door blocks, depending on the strength class, must withstand the action of static loads in accordance with the requirements of Table 2, which characterize the deforming ability of the door block, including resistance to extrusion, as well as the strength of fastening the door leaf to the frame.

5.3.4 Door blocks must withstand the action of operational dynamic loads during opening and closing (imitation of a hit on a slope, hitting an obstacle, hitting a foreign object in the porch). Schemes for applying dynamic loads are shown in Figures B.1-B.3 of Appendix B.

Dynamic loads created when testing the door with a freely falling load (solid body) are shown in Table 5.

Table 5 - Dynamic loads created by a freely falling load (solid body)

5.3.5 Door blocks, depending on the strength class, must withstand the impact of a soft inelastic body in accordance with the requirements of Table 6 when determining the strength (reliability) of fastening the door leaf to the frame. Door leaves are tested on both sides.

Table 6 - Impact (dynamic) loads created by the load (soft inelastic body)

The layout of the impact points on a single-leaf door block during the impact resistance test with a soft inelastic body (load) in the direction of opening the door leaf is shown in Figure 6.4 of Appendix 8.

GOST 31173-2016

5.3.6 When determining the strength of the structure, the material of the leaf and the quality of the finish, door blocks must withstand shock (pendulum) loads created by the load (solid body). The values ​​of shock (pendulum) loads are given in Table 7.

Table 7 - Impact (pendulum) loads created by a load (solid body)

5.3.7 Door blocks of group G of ordinary and reinforced categories (entrances to buildings, entrances to apartments), made in a burglar-resistant design, must comply with the requirements of regulatory documents 1 'in force on the territory of the state party to the agreement that adopted this standard.

5.3.8 Burglary resistance classes of group D door blocks and burglary resistance time are given in Table 8.

Table 8 - Classes of resistance to burglary of door blocks of group G

5.3.9 The force applied to the door leaf when closing until the required compression of the sealing gaskets, depending on the weight of the leaf, should not exceed 120 N. In this case, the latch and the deadbolt of the lock should work without jamming in the closed position. The force required to open the door leaf should not exceed 75 N (ergonomic requirements), for group B door blocks - 50 N.

Note - When evaluating the forces applied to the door leaf, it should be borne in mind that when testing group A door blocks, the pressure difference between rooms, rooms and

*) In the Russian Federation, wheel-resistant door blocks must comply with the requirements of GOST R 51242-98 “Protective mechanical and electromechanical structures for door and window openings. Technical requirements and test methods for resistance to destructive influences,

2) In the Russian Federation, a set of tools used in testing to determine the burglary resistance class of group G door blocks must comply with the requirements of Table 1 of GOST R 51242-98 “Protective mechanical and electromechanical structures for door and window openings. Technical requirements and test methods for resistance to destructive influences”, appendices B of GOST R 50862-2011 “Safes, safe rooms and storages of valuables. Requirements and test methods for resistance to burglary" and appendices B GOST R 52582-2006 "Locks for protective structures. Technical requirements and test methods for resistance to criminal unlocking and hacking.

GOST 31173-2016

outside or sudden wind load, and the presence of built-in safety devices and door closing devices. It should also be borne in mind that for door blocks intended for the passage of people with disabilities, the opening force should not be more than 5 N.

5.3.10 8 In the case of using artificial or natural leather, wood, wood-based materials, including those with natural or synthetic veneer, for cladding door panels, the cladding material must withstand without destruction an impact by a metal ball weighing 1 kg from a fall height of 1 m.

5.3.11 Appearance of products: color, permissible surface defects of facing materials and painted elements (risks, scratches, etc.) must correspond to standard samples approved by the head of the manufacturer.

Differences in color, gloss and surface defects visible to the naked eye from a distance of 0.6-0.8 m in natural light of at least 300 lux. not allowed.

5.3.12 Welded joints must be strong and meet the following requirements:

The metal of the welded joint and the boundary zone must not have cracks. Seam craters at the places where welding stops (ends) must be overcooked (welded);

Welded joints should have a smooth or evenly scaly surface without sharp transitions to the base metal;

Welded joints must be tight along the entire length and not have burns, narrowing, surfacing. indigestible. slag inclusions, etc.

5.3.13 The tensile strength of the metal of the welded joint shall not be lower than the requirements for the base metal.

5.4 Requirements for materials, accessories and gaskets

5.4.1 Materials and components used for the manufacture of door blocks must comply with the requirements of standards, specifications, technical certificates approved in the prescribed manner.

5.4.2 Materials and components must be resistant to climatic influences and have corrosion resistance in accordance with the regulations for these materials and components.

For door blocks used as entrances to the building and in contact with the external environment, it is recommended to use galvanized steel or steel with another type of protection that provides corrosion resistance of at least 240 hours of salt spray testing.

8id (type of protection) must be indicated in the product passport.

Requirements for corrosion resistance of locks and hardware - in accordance with GOST 538.

5.4.3 The surfaces of steel elements of boxes and sheets should not have cracks, mechanical damage, pits, distortions, rust. On the front surfaces of steel elements, slight local depressions, risks, waviness up to 0.5 mm deep are allowed, which do not reduce the functional properties and quality of products.

5.4.4 Steel parts of structures should be made of steel grades that ensure the strength and performance characteristics of structural elements, welded, bolted and other connections, depending on the nature and conditions of their work.

5.4.5 Sealing gaskets should be made of weather- and frost-resistant elastomer materials in accordance with GOST 30778.

5.4.6 Glued wooden cladding panels must comply with the requirements of GOST 30972. Profile molded wooden parts - GOST 8242.

5.5 Requirements for locking devices and hinges

5.5.1 In the manufacture of door blocks, locking devices, hinges and auxiliary parts intended for use in steel door blocks are used. Examples of designs of locks and hinges are shown in Figures B.5-B.7 of Appendix B.

GOST 31173-2016

A type. the number, location and method of fastening of locking devices and hinges are set in the working documentation, based on the size and weight of the opening elements of the product and the operating conditions of the door blocks. It is recommended to hang door panels on two hinges. Cloths of door blocks weighing more than 200 kg. as well as those used in public buildings with high traffic *, it is allowed to hang on three hinges, if recommended by the manufacturer of the hinges. At the same time, the recommended location of the middle hinge is 150-200 mm lower than the top one.

5.5.2 For hanging door panels on a frame (frame), it is recommended to use overhead bearing or other hinges with the ability to adjust in different planes in accordance with GOST 5088.

5.5.3 Locks in accordance with GOST 5089 of at least class III must be installed in door blocks of groups A and B, in door blocks of groups C. 61 - locks of at least class II, in door blocks of group D - locks of at least class IV.

To improve the protective properties of door blocks, it is recommended to use multi-bolt locks with locking along the perimeter of the door block or locks with rods with additional locking in the upper and lower horizontal frame profiles.

For door blocks of groups A. B. G. installed in rooms equipped with a burglar alarm. it is recommended to install locks of classes III-IV according to GOST 5089 with an early response security system.

Note - When choosing locking devices (locks with various types of security mechanisms, multi-bar locking system, etc.), it must be borne in mind that the first attempts to open door structure begin with an attempt to open the lock (locks) by destructive and ^ or non-destructive methods of opening. Therefore, the choice of a lock (locks) should be carried out on the basis of its (their) compliance with GOST 5089 with the assignment of a class according to the following parameters: mechanical strength, resistance to opening (breaking).

5.5.4 Locking devices must ensure reliable locking of opening elements of door blocks. Opening and closing should be easy, smooth, without jamming.

5.5.5 The design of the locking devices and hinges shall ensure tight and uniform crimping of the sealing gaskets along the entire contour of the seal and the porches.

5.5.6 Door appliances and fasteners must comply with the requirements of GOST 538 and have a protective and decorative (or protective) coating in accordance with GOST 9.303.

5.5.7 If door blocks are installed on evacuation routes in public buildings, including kindergartens, schools, hospitals, emergency door opening devices should be used to Anti-panic, allowing for quick evacuation. Requirements for anti-panic devices - according to GOST 31471.

5.6 Finishing requirements

5.6.1 In the manufacture of door blocks, apply different kinds finishes:

* coloring:

Facing with various materials;

Pasting with decorative (film) materials:

With the use of glass and double-glazed windows.

The type of finish is specified in the order.

5.6.2 As finishing materials, artificial and natural leather, decorative films, MDF boards (with natural or synthetic veneer, smooth or milled), wood, mirrors, plastic, fiberboard, paint and varnish and other materials are used in accordance with the requirements of regulatory documents for these materials. When choosing finishing materials, the operating conditions of the products should be taken into account.

5.6.3 Requirements for the finishing coating (lining) may be established by agreement between the manufacturer and the consumer in the contract (order) for the manufacture (supply) of products. In this case, it is allowed to evaluate the quality of the finish using reference samples agreed with the customer.

GOST 31173-2016

5.6.4 Metal surfaces of components before applying a paint or polymer coating must comply with the requirements of GOST 9.402. Requirements for paint coatings - according to GOST 9.401. coating class not lower than IV. designation of coatings - according to GOST 9.032.

5.6.5 The quality of surfaces with finished paintwork must comply with the requirements of GOST 9.032. In this case, it is recommended to apply the first layer with a primer paint, subsequent layers with protective and decorative paints and varnishes.

5.6.6 The front surfaces of the door blocks should not have cracks, burrs, mechanical damage. Surface defects visible to the naked eye from a distance of 1.5 m in natural light of at least 300 lux. not allowed.

The requirements for front surfaces are set in the manufacturer's technical documentation and / or in supply contracts, taking into account GOST 9.301 and GOST 9.032.

Non-facial surfaces of products may have recesses, risks, waviness and other defects that do not reduce the functional properties and quality of products.

Hole edges must be free of burrs and burrs.

5.6.7 Color (tone) and degree of gloss (gloss, dullness) of the finishing coating must correspond to standard samples approved by the head of the manufacturer and agreed with the customer.

5.6.6 Paint coatings must have an adhesive strength (adhesion) with the surface to be trimmed of at least 2 points, determined by the lattice notch method in accordance with GOST 31149.

5.6.9 It is recommended to establish the thickness of paint and varnish coatings, as well as the procedure for monitoring this indicator, in the technological documentation for the manufacture of products.

5.6.10 Protective and protective and decorative coatings must be resistant to temperature and humidity operational impacts.

5.6.11 Facing door panels are made from MDF boards according to regulatory documents or from various types of wood. MDF boards can be finished with sliced ​​veneer according to GOST 2977, peeled veneer according to GOST 99 or synthetic veneer according to regulatory documents. It is allowed to use milled or smooth MDF boards.

5.6.12 The front surfaces of wood parts used for finishing door panels should not have processing defects and wood defects, with the exception of curl. tortuosity, eyes, fiber inclination up to 5% according to GOST 2140.

The roughness of the front surfaces of wood parts R m should not be more than 60 microns in accordance with GOST 7016. The moisture content of the wood should be in the range from 8 to 12%.

5.6.13 The design of fastening of facing parts made of wood and board materials to steel elements of door blocks should provide the possibility of compensating their temperature and humidity deformations.

The shape and dimensions of the sections of the facing profiles adjacent to the steel surfaces of the outer products must provide a minimum area of ​​contact with these surfaces. as well as the possibility of ventilation of the cavity between them, otherwise the contact surfaces must be protected by paintwork or other protective materials.

5.6.14 Double-glazed windows used in the construction of door blocks must comply with GOST 24866. It is recommended to use double-glazed windows with reinforced types of glass: tempered glass - according to GOST 30698; laminated glass - according to GOST 30826.

For glazing door blocks of group G, it is recommended to use as external glass: laminated glass - according to GOST 30826. tempered glass - according to GOST 30698.

5.6.15 The design solutions for the fastening units of double-glazed windows (glasses), as well as the filling panels of the opaque part of the door unit, should prevent the possibility of their dismantling from the outside. The fastening of the layouts should not cause pinching and point stresses in the glass.

5.6.16 Double-glazed windows (glasses) are mounted using sealing gaskets made of elastomeric materials in accordance with GOST 30778.

5.7 Completeness and marking

5.7.1 8 depending on the purpose of the door blocks in the design documentation, as well as when placing orders, it is necessary to provide for the complete set of products with valves, door closing devices (closers), opening angle limiters (stops), eyes, chains, etc.

GOST 31173-2016

5.7.2 The complete set of door blocks when they are delivered to the consumer must comply with the requirements. specified in the contract (order).

Products should be delivered assembled with locking devices installed.

The set of keys must be handed over to the customer in a sealed form against the signature of the customer (buyer).

5.7.3 the delivery set should include a quality document (passport) and an operating manual for door blocks, including recommendations for installation.

5.7.4 Each door block is marked with a label indicating the name of the manufacturer. type, reference designation of the product indicating the strength class, date of manufacture and / or order number, sign (stamp) confirming the acceptance of the product by the technical control service. Product labeling must reflect the actual requirements for the type of door specified in the order. as well as the possibility of carrying out identification in order to establish the authenticity of the manufacturer, indicated by the manufacturer.

5.7.5 The door devices included in the product must be marked in accordance with the regulatory documents for these devices.

5.8 Rules for installation (assembly) of locks

5.8.1 Before installing the lock on the door, it is necessary to check its functioning - closing and opening from both sides of the lock, the operation of the latch from the handles, the key, the presence and operation of transcoding devices.

5.8.2 Installation of locks when assembling a door flea in a door production environment

5.8.2.1 The design of the door block shall provide for a special niche(s) for installing a specific lock(s).

5.8.2.2 The lock niches must be free from voids, foreign objects (fillers, insulation, chips, etc.), which can disrupt the normal operation of the lock.

5.8.2.3 All necessary holes (fixing holes, technological holes, places of improvement for the installation of the lock) are made according to the markings made according to the template included in the lock kit. The use of the lock as a conductor for marking when inserting the lock is not allowed in order to prevent clogging of the lock mechanism with chips.

5.8.2.4 When installing a lock with vertical rods, it is necessary to ensure their free movement. excluding contacts with internal parts of the door structure. It is allowed to use intermediate guides to ensure the longitudinal rigidity of the rods.

5.6.2.5 When installing a lock with a front plate, an easily detachable connection of the lock rods with external vertical rods should be used, which is carried out when the lock is inserted into the lock niche from the end of the door, or a hatch should be provided on the inside of the door leaf.

5.8.2.6 Availability of a hatch when mounting a lock without a front plate (on bollards) from the inside for maintenance of the lock, vertical rods at the points of connection with the rods of the lock or its replacement is mandatory. Access to the lock can also be provided by the presence of a removable decorative cladding panel that covers the entire interior of the door leaf.

Note - When installing the lock according to 5.8.2.6, it should be borne in mind that the first stroke of the bolt will be a passage through the wall of the door leaf frame. In this case, locks with bolts protruding from the body should be ordered. When installing, you need to follow that. so that the bolt, passing through the frame, does not touch it and exits freely.

5.8.2.7 Before inserting the lock into the kit for final installation, clean the kit from foreign objects and debris.

5.8.2.8 When assembling the lock, significant forces and impacts on the cylinder mechanism should be avoided.

5.8.2.9 Fastening of locks should be carried out with screws; fastening of locks by welding is not recommended.

5.8.2.10 For security purposes, at least two locks or one lock with two secret mechanisms are installed on the door blocks of groups A. B. D, one of which must be with

GOST 31173-2016

latch, the other should fix the door leaf in the closed position, after which the locks are locked. Locks should be adjusted like this. so that the bolts come out freely, without touching the walls of the inlet of the door frame (for clearance recommendations, see paragraph 6.1.8 of GOST 5089). The inlet in the door frame for the entry of the deadbolt shall be cleaned in accordance with 5.8.27.

Note vcha niv - For door blocks of group A. installed in public buildings, it is recommended to use electromechanical (electronic) locking devices.

5.8.2.11 When mounting the cylinder lock and installing the cylinder mechanism, the length of the cylinder mechanism and the asymmetry with respect to the middle of the leash must be chosen so that the cylinder mechanism protrudes from the outside of the armor plate by no more than 3-5 mm. When installing the armor plate, the length of the cylinder mechanism is chosen taking it into account.

5.8.2.12 After assembling the door block, make sure that the locks are functioning normally.

5.8.2.13 Finished door units should be transported with the locks "open" to prevent possible deformation of the crossbars during transportation.

5.8.2.14 Installation of the door block in the opening should be carried out by manufacturers of door blocks or an organization for installing door blocks in accordance with GOST 30971 or regulatory documents. establishing requirements for the installation of door blocks in openings. General requirements for the installation of door blocks are given in Appendix D.

Note - When forming the design of the junction mounting units, it is necessary to take into account the scope of the door blocks, the features of the thermal expansion of door frames and door panels, and the requirements for burglary resistance.

5.8.2.15 Before installation, the door unit should be freed from packaging, check that possible packaging residues (especially polyethylene) are not drawn into the gaps between the deadbolt and the lock body.

5.8.2.16 After installing the door block in the opening, before final sealing, check the operability of the door leaf and locks.

Notes and c - When using mounting foam for sealing, it is necessary to exclude the possibility of its getting into the door frame, into the zone of movement of the deadbolt to prevent disruption of the normal functioning of the lock.

5.8.3 Installing a lock in a functioning front door

5.8.3.1 8 If it is necessary to improve the security properties of a functioning door, an additional lock is installed in a new place on the door leaf.

5.8.3.2 Additional and already installed locks must be with different security systems. If there is a lock with a latch on the door leaf, then the additional lock intended for installation must be without a latch.

5.8.3.3 Before installing an additional lock, inspect the interior of the door leaf (removable panel on the inside, a hatch under the upholstery or a removable wall, etc.) so that when the door frame breaks, it does not get into the reinforcement or partition.

5.8.3.4 Marking for insertion of an additional lock must be carried out according to the scheme included in the delivery set, or according to the dimensions of the lock.

5.8.3.5 The niche cavity must be freed from foreign objects and debris in such a way. so that the lock enters it freely. In order for the new niche not to be isolated from the rest of the cavity of the door leaf, it is necessary to exclude the possibility of getting into the lock mechanism during operation of the door fragments of foreign objects that may affect its normal operation.

5.8.3.6 When mounting the lock, forces and impacts on the cylinder mechanism are not allowed.

5.8.3.7 It is not allowed to drill the walls of the door block to correct the location of the key channel or the cylinder mechanism with the lock inserted into the niche.

5.8.3.8 The hole for the passage of the bolt of the lock into the door frame must ensure the free passage of the bolt while holding the door leaf with the latch.

5.8.3.9 When choosing a cylinder mechanism, its reliability class should be taken into account depending on the area of ​​application in accordance with Table 1 of GOST 5089.

5.8.3.10 It is recommended to purchase the cylinder mechanism after installing the lock, considering that the lock may not be installed in the middle part of the door thickness. In this case, the cylinder mechanism must be asymmetrical with respect to the middle of the driver.

GOST 31173-2016

Note - The length and symmetry of the cylinder mechanism can be calculated by focusing on the end of the door leaf and the middle of the bolt of the lock, taking into account the end plates. The cylinder mechanism should not protrude from the lining (at least from the outside) by more than 3-5 mm. If it is planned to install an armor plate. then the dimensions of the cylinder mechanism are adjusted to take it into account. Installation of the armor pad gelagen. as it increases the resistance of the cylinder mechanism assembly x to breaking.

5.9 Malfunction and warranty service of the lock

Violation of the normal operation of the lock, caused by its improper operation, as well as the appearance of any changes in the lock that are not provided for by the design, remove the obligations of the manufacturer (dealer) for warranty service.

Notes

1 Locks are not lubricated during operation (except for what was lubricated at the enterprise). It is allowed to carry out preventive cleaning of the cylinder mechanism once a year with WD-40 or silicone-based aerosols.

2 In case of specific changes in the operation of the lock, please contact the service department.

3 High class cylinder keys are packed in black plastic bags. It is not allowed to open packages with keys without making sure that the cylinder mechanism is suitable, otherwise its exchange may be refused.

4 Key copy cards are included in the high-end cylinder mechanism kit. Without presenting a copy card, orders for the production of duplicate keys are not accepted.

6 Acceptance rules

6.1 Door blocks must be accepted by the manufacturer's technical control service for compliance with the requirements of this standard, as well as the conditions specified in the contract for the manufacture and supply of products. Confirmation of acceptance of products by the technical quality control service is the execution of a document (passport) on the acceptance of products.

6.2 The quality of door units established by this standard is confirmed by:

Incoming control of materials and components:

Operational production control;

Every shift acceptance control of finished products;

Control acceptance tests of each batch of products, carried out by the technical control service of the manufacturer;

Periodic and certification tests of products in independent test centers:

Qualification tests.

6.3 The procedure for conducting incoming and operational production control at workplaces is established in the technological documentation.

In the event that the manufacturer completes the door blocks with parts of its own manufacture. they must be tested and accepted in accordance with the requirements of regulatory documents for these parts.

6.4 The list of indicators controlled during the shifts of acceptance control of finished products. acceptance tests of each batch of products and during periodic tests, is given in table 9.

Table 9

GOST 31173-2016

End of table 9

Us

Claim number

tests

Type of control"

Periodicity (at least)

Operation of hinges and locking devices

Marking

Visually

For control type 1 - once per shift, for type II - each batch

Controlled nominal dimensional deviation*’ and edge straightness

According to 7.2.1. 7.2.2

For control type 1 - once per shift, for type II - each batch

Quality of welded joints

For control type 1 - once per shift, for type II - each batch

For control type II - once per shift

Once every three years

Once every three years

Impact resistance of a soft inelastic body

Once every three years

Solid body impact resistance

Once every three years

Reliability

5.3.1. table 4

Once every three years

Ergonomic Compliance

Once every three years

Reduced resistance to heat transfer

5.3.1. table 4

Breathability

5.3.1. table 4

When put into production

Hack resistance

Soundproofing

5.3.1. table 4

When put into production. design change. material replacement

Correct installation of the lock

Once per shift

" Type of control:

I - "Every shift acceptance control:

II - control of each batch (acceptance tests), carried out by the technical quality control service of the manufacturer;

III - control during periodic tests carried out in independent testing centers.

"* Controlled nominal dimensions for test type II are established in the technological documentation.

GOST 31173-2016

6.5 Appearance. tightness of sealing gaskets, operation of hinges and locking devices, marking and quality of welded joints are checked by the method of continuous control.

6.6 Finished door blocks that have passed control are marked. Products that do not pass the control of at least one indicator are rejected.

6.7 To conduct acceptance tests for each batch of door blocks, conducted by the technical quality control service of the manufacturer, samples of door blocks are taken from a batch of products by random selection in the amount of 3% of the batch volume, but not less than 3 pcs. 8 if there are less than three products in the batch, each product is subjected to control.

In the event of a negative test result for at least one indicator of at least one sample, the quality of the products is re-checked on a double number of samples for the indicator that had a negative test result.

If a discrepancy between the indicator and the established requirements is detected again, at least on one sample, the controlled and subsequent batches of products are subjected to continuous control (sorting). With a positive result of continuous control, they return to the established procedure for acceptance tests.

6.8 Periodic performance tests as specified in 5.3.1. 5.3.3-5.3.8 are carried out when putting into production, when making changes to the design of the door unit or the technology of their manufacture, but at least once in the period specified in Table 9. as well as during product certification. In 8 justified cases, it is allowed to combine periodic and certification tests (certification tests are carried out in the scope of periodic tests).

Qualification tests are carried out for all indicators when putting products into production.

Tests are carried out in test centers accredited for the right to conduct them.

Tests to determine the reduced resistance to heat transfer, air permeability. Sound insulation is applied to structures designed to absorb these loads in accordance with their area of ​​application.

6.9 The consumer has the right to conduct a quality control check of the door blocks, observing the sampling procedure and test methods specified in this standard.

When accepting products by the consumer, a batch is considered to be the number of products shipped for a specific order, but not more than 90 pieces, drawn up with one quality document.

Table 10 - Single step quality control plan

Note - Significant and critical defects include: defects. leading to loss of operational characteristics, irreparable without replacement of a part of the product (breakage of a steel profile, etc.), exceeding the maximum deviations of dimensions established in normative documents, more than e 1.5 times, understaffing of products.

Minor defects include removable defects: minor surface damage, unadjusted door fittings and hinges, exceeding the maximum deviations of dimensions established by regulatory documents by less than 1.5 times.

GOST 31173-2016

By agreement of the parties, the acceptance of products by the consumer is allowed to be carried out in the warehouse of the manufacturer. at the consumer's warehouse or in another place specified in the supply contract.

6.11 Each batch of door blocks must be accompanied by a quality document (passport). An example of filling out a product passport is given in Appendix D.

6.12 Acceptance of door blocks by the consumer does not release the manufacturer from liability in case of detection of hidden defects that led to a violation of the performance characteristics of products during the warranty period.

6.13 General requirements for incoming inspection when supplying door blocks to

construction sites or private consumers

6.13.1 Upon delivery of door blocks to the facility, the manufacturer is obliged to confirm their compliance with the current regulatory documents, as well as the requirements of the project (if any). The specified requirement is documented in the form of a package of accompanying documentation. The supporting documentation package should include:

Product passport according to Appendix D:

Test reports in accordance with sections 7.2 and 7.3;

Technical, engineering calculations (if any) confirming performance in accordance with 5.3.1.

Regulatory document for the installation of products subject to the conclusion of a single contract for the manufacture and installation of products.

6.13.2 During the input control of door blocks delivered to the facility or transferred to specialized dealer centers, the following is checked:

Number of products installed in the order:

Product type;

Availability of marking (in accordance with 5.7);

Overall dimensions (optional):

Appearance (presence of defects);

Completeness (in accordance with the order);

The presence of a package of accompanying documentation.

6.13.3 Based on the results of the input control at the facility, an act of acceptance and delivery of door blocks is drawn up.

Note - If as a result of storage of ish after installation of products, defects are found. not determined upon acceptance of products, the manufacturer is not responsible for this.

7 Methods of control and testing

7.1 Methods of control and testing during incoming and production operational control are established in the technological documentation.

7.2 Methods for determining the indicators controlled during the daily acceptance control and control acceptance tests are given in 7.2.1-7.2.7.

7.2.1 The geometric dimensions of the door blocks and the straightness of the edges are determined using the methods established in GOST 26433.0 and GOST 26433.1.

Limit deviations of the nominal dimensions of product elements, the difference in the lengths of the diagonals and other dimensions are determined using a metal measuring tape according to GOST 7502. calipers according to GOST 166. probes according to regulatory documents.

The maximum deviations from the straightness of the edges are determined by applying a calibration ruler in accordance with GOST 8026 or a building level with a flatness tolerance of at least the 9th degree of accuracy in accordance with GOST 9416 to the part under test and measuring the largest gap using probes according to regulatory documents.

7.2.2 The maximum deviations of the nominal dimensions of the gaps under the overlay are checked using a set of probes or a ruler in accordance with GOST 427.

7.2.3 The sag in the mating of adjacent parts lying in the same plane is determined with a feeler gauge as the distance from the edge of the ruler according to GOST 427, applied to the upper mating surface, to the lower surface.

GOST 31173-2016

7.2.4 Appearance. the quality of welded joints, the color and quality of the finish of the door blocks are evaluated visually by comparison with standard samples approved by the head of the manufacturer. from a distance of 1.5 m in natural light of at least 300 lux.

7.2.5 Adhesion (strength of adhesion of paint and varnish coatings to the metal surface) is determined by the lattice notch method according to GOST 31149.

7.2.6 Tight fit and correct installation of gaskets, door fittings. fasteners and other parts, color and absence of cracks in welded joints, marking and packaging are checked visually.

To determine the tightness of sealing gaskets, compare the dimensions of the gaps in the porches and the degree of compression of the gaskets, which should be at least 1/5 of the height of the uncompressed gasket. Measurements are carried out with a caliper according to GOST 166 or a ruler according to GOST 427.

The tightness of sealing gaskets with closed sheets can be determined by the presence of a continuous trace left by a coloring matter (for example, colored chalk), previously applied to the surface of the gaskets and easily removed after inspection.

7.2.7 The operation of the door hinges is checked by tenfold opening and closing of the leaf elements of the product, in case of detection of deviations in the operation of the door hinges, they are adjusted and re-checked.

7.3 Methods for determining the indicators controlled during periodic tests are given in 7.3.1-7.3.10.

7.3.1 The reduced resistance to heat transfer is determined in accordance with GOST 26602.1.

7.3.2 Air and water permeability is determined according to GOST 26602.2.

7.3.3 Sound insulation is determined according to GOST 26602.3.

7.3.4 Wind load resistance is determined according to GOST 26602.5.

7.3.5 Indicators of reliability, resistance to static, dynamic, shock loads and ergonomic indicators of door blocks are determined according to the methods of testing laboratories, Appendix B of this standard and GOST 30777.

Tests of locking devices for reliability, load resistance and compliance with ergonomic requirements are carried out on special equipment (stands) according to regulatory documents. programs and methods of testing laboratories.

After testing, the product must remain operational.

When testing to determine the resistance to dynamic loads, the load that occurs when the door leaf is suddenly opened (for example, during a draft) at the moment of contact of the door leaf with the slope of the doorway.

The test to determine the impact resistance of a soft inelastic body is carried out with a three-time impact, for example, a pear with a diameter of the lower part (300 ± 5) mm and a mass of (30 ± 0.5) kg, from a height of fall according to 5.3.4 into the central zone of the sample. After testing, the residual deformation shall not exceed 2 mm.

Upon completion of the tests, the door blocks must remain operational, while the bolt of the lock and the latch must freely enter their counterparts.

Before and after testing the door units for failure-free operation, it is recommended to check the tightness of the seals in accordance with 7.2.6.

When testing door blocks to determine the resistance to a static load (see Appendix B) acting perpendicular to the plane of the door leaf in the free corner zone, it is recommended to use the graph of free corner deflection versus the applied load given in Appendix A.

When applying a load in the plane of the door leaf, the leaf must be open at 90° with respect to the frame. The load is applied in the area of ​​the free corner, kept for at least 5 minutes. Deformation is analyzed, including tearing of a loop from a web or box.

7.3.6 When testing door blocks to determine the resistance to impact load created by a solid body, a three-time impact is carried out in the center of the door leaf and, if necessary, in the corner zones with a solid body weighing 2 kg. The average impact damage diameter shall not exceed 2.0 mm. depth - 1.5 mm. After testing, the door blocks must remain operational.

7.3.7 Corrosion resistance of metal of door blocks and locking devices is determined in accordance with GOST 9.308, GOST 538 and regulatory documents for specific products.

GOST 31173-2016

7.3.8 Lock products must be tested with the subsequent assignment of a class of resistance to opening and burglary in accordance with GOST 5089. GOST 19091. as well as with regulatory documents 1 *. operating in the territory of the state party to the agreement that has adopted this standard.

7.3.9 Wind loads on door blocks of group A are measured according to the normative documents for test methods, taking into account the fact that the entrance doors to the buildings are located on the first floors of the buildings. After testing, the deflection value shall not exceed 6 mm. Structural elements must withstand wind loads without damage, the door leaf must be closed (all locking devices must be engaged).

Note - Destruction and replacement of glass or double-glazed windows is allowed.

7.3.10 Quality control methods for welded joints are established in the manufacturer's technical documentation in accordance with GOST 5264.

7.3.11 Burglary test

7.3.11.1 Burglary resistance tests are carried out on door blocks with enhanced protective functions in accordance with the regulatory documents for test methods, including in accordance with the regulatory documents 2) in force on the territory of the state party to the agreement that adopted this standard. Tests are carried out on door blocks in the direction of opening the door leaf until the sample is destroyed, i.e., until the door is opened or until the state in which the leaf is jammed due to deformation and further continuation of the test does not make sense.

7.3.11.2 Burglary resistance is determined by the time spent on breaking, and depending on the type of tool used. Requirements for a tool for manual hacking - in accordance with regulatory documents 3) in force in the territory of the state party to the agreement that has adopted this standard.

7.3.11.3 The protection class of laminated glass is determined according to GOST 30826.

Note - If there are documents confirming the glass protection class, it is allowed during the testing process not to apply static and dynamic loads to the double-glazed window.

8 Packaging, transport and storage

8.1 Packaging of door blocks should ensure their safety during storage, handling and transportation.

8.2 Devices or parts of devices not installed on door blocks must be packed in polyethylene film in accordance with GOST 10354 or in other packaging material that ensures their safety, firmly tied up and delivered complete with products.

8.3 Before transporting the door blocks, it is recommended to fix or secure the door leafs in any way that ensures their safety during transportation.

8.4 Door blocks are transported by all means of transport in accordance with the rules for the carriage of goods in force for this type of transport.

8.5 During storage and transportation of door blocks, they must be protected from mechanical damage and the effects of precipitation.

8.6 During storage and transportation, it is recommended to install gaskets made of elastic materials between the products.

In the Russian Federation, GOST R 52582-2006 “Locks for protective structures. Technical requirements and test methods for resistance to criminal unlocking and hacking *.

2 > In the Russian Federation, test methods are carried out in accordance with GOST R 51242-98 “Protective mechanical and electromechanical structures for door and window openings. Technical requirements and test methods for resistance to destructive influences”.

3) In the Russian Federation, a tool used in the test to determine the resistance to burglary. must meet the requirements! GOST R 51242-98 “Protective mechanical and electromechanical structures for door and window openings. Technical requirements and test methods for resistance to destructive influences”. GOST R 50862-2011 Safes, safe rooms and valuables storage. Requirements and test methods for resistance to breaking” and GOST R 52582-2006 “Locks for protective structures. Technical requirements and test methods for resistance to criminal unlocking and hacking.

GOST 31173-2016

8.7 Door blocks are stored in a vertical or horizontal position on wooden linings, pallets or in special containers in covered rooms in accordance with GOST 15150 (UHL. HL versions).

9 Manufacturer's warranties

9.1 The manufacturer guarantees the compliance of the door blocks with the requirements of this standard, subject to the rules of transportation, storage, installation, operation, as well as the scope established in the regulatory documents and project documentation.

9.2 Upon agreement with the consumer (customer), the manufacturer provides service, including emergency opening of doors in case of loss or breakage of keys, advice on the use and operation of door devices and locking devices, and repair of products.

9.3 The warranty period for the operation of door blocks is established in the supply contract, taking into account the operating conditions:

> at least one year from the date of shipment for door external entrances to buildings of blocks of groups A and G with a high intensity of passage with the risk of negligence;

At least three years from the date of shipment for door units of groups B and C with an average volume of passage and with a limited risk of negligence:

At least two years from the date of shipment for door units of group B1 with a low level of traffic and the risk of negligence.

9.4 Warranty period of storage of door blocks is one year from the date of shipment of products by the manufacturer, provided that they are stored in accordance with Section 8.

GOST 31173-2016

Annex A (informative)

An example of determining the strength class of door blocks

This appendix provides an example of determining the strength class of a door block by the value of a static load acting perpendicular to the plane of the door leaf in the area of ​​the free corner.


KN, M2, US, W, Mb "kpshshfochnyut;

Grvfmi regul mg * t test dvernyk blocks;

Odoanvchoniv rvdugtatos yaslpi zhy door Vzhzhyav ovoshvtopchiorzh vmtrolmyim load

Figure A.1 - Graph of the dependence of the deflection L1 of the free corner of the leaf on the applied load P when testing door blocks to determine the resistance to a static load acting perpendicular to the plane of the leaf in the area of ​​the free corner

GOST 31173-2016

Annex B (informative)

Examples of designs of door blocks and options for filling door panels

I - upper locking crossbar; 2 - upper link of the main lock: 3 - web frame (welded steel profiles);

4 - places of fastening of the internal hatch; 5 ■- valve. b - the place of attachment of the upper link; 7 - crossbars of the lock sueapianoto; 8 - latch; 9 - deadbolt of the cylinder lock; 10 - lower link of the main lock; 11 - places for fastening the finish;

12 - internal cavity for filler; 13 - vertical link guide; 14 - lower locking rib,

15 - mounting kushko "; 15 - port; 17 - peephole; 15 - loop knot. 19 - outer steel sheet;

21 - combined double-cylinder lock; 22 - box (frame); 23 - mounting anchor.

24 - grotivosemny passive crossbar (pin); 2S - hole for anti-removable caliper (pin)

Figure B.1 - An example of the design of a door block, the leaf of which is welded from two stagnant sheets or with an outer steel sheet and an inner sheet of fiberboard and steel profiles, a box (frame) -

from bent steel profile

GOST 31173-2016


Door leaf with two steel sheets, steel box profiles and honeycomb core 6


Door leaf with an outer steel sheet and an inner sheet of fiberboard, with profiles of complex cross-section and a filling of wood yoke with mineral insulation


Door leaf of the "bent box" type * with U-shaped steel profiles and foam filling g


Door leaf with outer steel sheet and inner sheet made of fiberboard. steel angle profiles with timber bars and foam filling

Figure B.2 - Options for filling the door leaf

GOST 31173-2016

1 - frame of the canvas of the xendeich type "(eeealcoy steel sheets): 2 - end reinforcement of the locking part of the canvas:

3 - high-density mineral wool board filling: 4 - Compliant reinforcing steel profile of the frame.

5 - all-metal profile of the frame with a casing: b - mounting plate: 7 - latch of the cylinder lock, b - side locking crossbars; 9 - cylinder lock: 10 - deadbolt box: 11 - lock striker:

12 - port: 13 - anti-removable passive crossbar (pin): 14 - end reinforcement of the lethal part of the canvas; fS - peephole; 16 - loop; 17 - web seal. Tb - frame seal: Tb - outer steel sheet;

20 - inner steel sheet, 21 - top cover of the canvas

Figure B.3 - An example of the design of a door unit with a "sandwich" leaf with two profiled and rolled steel sheets, with L-shaped steel reinforcing profiles and a filling of high density mineral wool, a box (frame) - from a steel all-metal profile complex shape, made by cold rolling galvanized steel


Sandwich type door leaf with two profiled and rolled steel sheets, with L-shaped steel reinforcing profiles and high-density material wool filling


Sandwich-type leaf with two profiled and rolled steel sheets, with L-shaped steel reinforcing profiles and polyurethane foam filling

Figure B.4. sheet 1 - Options for filling the door leaf of the "sandwich" type

GOST 31173-2016


Sandwich-type door leaf with two profiled and welded steel sheets, with L-shaped steel reinforcing profiles and polyurethane foam filling with cladding made of wood or wood-based materials (horizontal section)

Figure B.4. sheet 2

d

and

Figure B.5 - Examples of door hinges on a support rod

GOST 31173-2016

e

O

e

Figure B.6 - An example of a mortise combination lock with two secret mechanisms

and vertical rods

Figure B.7 - Example of a bolt lock


Figure B.8 - An example of an elastic seal of a special shape with a leg for installation in a groove

GOST 31173-2016

Annex B (mandatory)

Methods for determining the resistance to static loads and schemes for applying dynamic loads

B.1 Resistance to static load applied in the plane of the door leaf

B, 1.1 When determining the resistance to a static load applied in the plane of the door leaf, the load (sequentially from smaller to larger) is applied to the open leaf by 90 ° in the direction from top to bottom in the free corner zone (application point is set) for 5 minutes.

B.1.2 After removal of the load, the presence (or absence) of permanent deformation is revealed. If the residual deformation fits into half of the gap between the leaf and the frame (in the lower and vertical parts of the door in the area of ​​the free corner) or is completely absent, the door passed the test.

8.2 Resistance to static load applied in the area of ​​the free corner of the door

blades perpendicular to its plane

B.2.1 When determining the resistance to a static load applied in the plane of the door leaf, the load (successively from smaller to larger) is applied in the direction of opening the door leaf (in this case, the door must be closed on all locks) 8 in the free corner zone (the application point is set) in within 5 min.

B.2.2 After removal of the load, the presence (or absence) of permanent deformation is revealed. If the permanent deformation (in the area of ​​the free corner) does not exceed 1/5 of the thickness of the seal (see 7.2.6). The door passed the test. Otherwise, a gap will open for the passage of air and the indicators of sound insulation and resistance to burglary will decrease.

B.3 Resistance to static load applied perpendicularly in the hinge area

door leaf plane

B.3.1 When determining the resistance to a static load applied in the hinge area perpendicular to the plane of the door leaf, the load (successively from smaller to larger) is applied in the direction of opening the band (the door must be closed with all locks) in the area of ​​each hinge (application points are given ) within 5 min.

B.3.2 After removal of the load, the presence (or absence) of permanent deformation is revealed. If the permanent deformation in the area of ​​each hinge does not exceed 1/5 of the thickness of the seal (see 7.2.6), the door passed the test. Otherwise, a gap will open for the passage of air and the indicators of sound insulation and resistance to burglary will decrease. Schemes for applying dynamic loads are shown in Figures B.1-B.3.

GOST 31173-2016

Figure B.1

drop height 4S0 mm. cargo weight 20 kg. thickness rubber gasket 40 mm

Scheme of application of dynamic load when hitting the opening angle limiter

GOST 31173-2016

pad

b - the height of the fall of the load 450 th. cargo weight 20 kg. thickness of the rubber pad 40 we

Figure B.2 - Scheme of application of dynamic load upon impact with a foreign object

and the porch when closing the canvas

GOST 31173-2016

I - clamp: 2 - locking device or limiter, 3 - flexible gross: 4 - flexible soft body (load) weighing 30 kg S - removable trick: A * "height of the load: a - angle of deviation of the load

Figure B.3 - Scheme of application of dynamic load during testing for impact resistance by a soft inelastic body (load) in the direction of opening the door leaf

GOST 31173-2016

Figure B.4 - Diagram of the location of impact points on a single-leaf door unit when testing for resistance to impact with a soft inelastic body (load) in the direction of opening the door leaf

General requirements for the installation of door blocks

D. 1 The requirements for the installation of door blocks are established in the design documentation for construction sites, taking into account the design options adopted by the 8th project for the design of the junctions of products to the walls, designed for given climatic and other loads.

D.2 Installation of door blocks should be carried out by specialized construction companies or specially trained teams of the manufacturer. Completion of installation work must be confirmed by a kg o * i of acceptance, including the warranty obligations of the manufacturer of the work.

D.3 At the request of the consumer (customer), the manufacturer (supplier) of door blocks must provide him with a standard installation instruction approved by the head of the manufacturer and containing:

Drawings (schemes) of typical mounting junctions:

List of materials used (taking into account their compatibility and temperature conditions of application);

The sequence of technological operations for the installation of door blocks.

D.4 When designing and executing junction nodes, the following conditions must be met:

The sealing of the mounting gaps between the products and the slopes of the openings of the wall structures must be tight, tight around the entire perimeter of the door block, designed to withstand climatic loads from the outside and operating conditions inside the premises:

The design of the junctions of external products (including the location of the door unit along the depth of the opening) should prevent the formation of cold bridges (thermal bridges) as much as possible, leading to the formation of condensate on the internal surfaces of doorways:

The operational characteristics of the structures of the junction points must meet the requirements established in the building codes and regulations in force on the territory of the state party to the agreement that adopted this standard.

A version of the mounting assembly of the internal door unit is shown in Figure D.1.


KSIP1PMCIPIN>L

t - box (frame | door block. 2 - mounting foam. 3 - outer seal, 4 - door leaf: S - inner seal, b - decorative frame portal: 7 - trim: c - mounting anchor.

9 - mounting "eye". 10- wall

Figure D.1 - Version of the mounting assembly of the internal door unit

GOST 31173-2016

D.5 Quantity and location of mounting "lugs", view. the diameter and length of the fasteners are set in the project documentation, taking into account the material of the walls and the design of the doorway. It is recommended to use building anchors with a diameter of at least 10 mm as fasteners for the installation of products. The distance between fasteners is at least 700 mm.

It is not allowed to use sealants, adhesives, adhesives, as well as building nails for fastening products.

D.b Door blocks should be installed according to the level and plumb. Deviations from the vertical and horizontal profiles of boxes of mounted products should not exceed 1.5 mm per 1 m of length, but not more than 3 mm for the height of the product. If the opposite profiles are deviated in different directions (“twisting into boxes), their total deviation from the normal should not exceed 3 mm.

The door block is installed in the prepared doorway symmetrically with respect to the central vertical of the opening. The deviation from symmetry should not exceed 3 mm in the direction of the slope of the opening, intended for fastening the profile of the box with hinges. Deviation from symmetry to the other side of the opening is not recommended.

D.7 To fill the mounting gaps (seams) of external products, mounting foam, silicone sealants, pre-compressed sealing tapes (PSUL) (compression tapes), insulating polyurethane foam cords, and flax heaters are used. mineral wool and other materials that have a hygienic conclusion and provide the required performance of the seams.

D.8 When arranging assembly joints and installing external door blocks, it is recommended to take into account the requirements of GOST 30971.

An example of filling out a door block passport

Passport (document of quality) of a steel door block, external, reinforced in accordance with GOST 31173-2016

(name of manufacturer)

(address, phone, fax of the manufacturer)

a) design - single-floor, right-hand execution, with a threshold, opening inwards:

b) overall dimensions - height 2300 mm. width 970 mm.

Conventional designation DSN. A. On. Prg. ext. P2ls. M3. UZ POST 31173-2016

Certificate of Conformity (if available)

(certificate number)

Completeness

a) the type of fabric finishing - combined (milled MDF board: wikilic similar);

b) type (type) of protection against corrosion of the material of the door block - galvanization:

c) door hinges - two overhead bearing hinges:

d) locking devices - level lock of class ... and a lock with a cylinder mechanism of class ...:

e) the number of contours of sealing gaskets - 2 contours:

e) additional information. The delivery set of the product includes: closer (closing regulator), door stop (opening limiter), operating instructions.

Tested performance

Reduced resistance to heat transfer 0.65 m 2 - "C / W.

Air permeability at DR 0 100 Pa - 15 me / (hm2).

Sound insulation 22 dB.

GOST 31173-2016

Reliability, opening and closing cycles 500,000.

Mechanical strength class M2.

The warranty period is at least one year.

Batch number

Order number/item in the order

Quality Control Receiver Date k_*_20_g.

manufacturing

(signature)

GOST 31173-2016

UDC 692.81-034.14(083.74):006.354 MKS 91.060.50

Keywords: door steel blocks, external and internal door blocks, buildings and structures, entrance door blocks to buildings and apartments, technical requirements, acceptance rules, control methods