Ip 212 3su connection diagram. Fire detector connection diagrams

  • 26.09.2020

The new generation of fire detectors IP 212-3SU, retaining all the advantages of its predecessors, is distinguished by even greater ease of installation and maintenance, high sensitivity in the absence of false alarms (including from fluorescent lamps), and low inertia. At the same time, the current consumption decreased by more than 2 times (up to 50 μA)! In addition, the new IP 212-3SU detector is made in a modern small-sized case, has a much more efficient testing system, is protected from dust and insects, its socket is designed to connect a fire-resistant FRLS and FRHF cable, and has a 5th contact for connecting an additional resistor in two-threshold loops. Modern design and technological solutions have made it possible to reduce the price of the updated IP 212-3SU.

Smoke chamber. The basis of the smoke optical-electronic detector is:

Rice. 1. Design IP 212-3SU

Optical pair - LED + photodiode (Fig. 1 a) and smoke chamber (Fig. 1 b, c), which determine the technical and operational characteristics. The two-level smoke chamber of the new IP 212-3SU detector was the result of a large amount of mathematical modeling and experimental research. Its lower part is perfectly coordinated with the horizontal smoke flows spreading under the ceiling. The vertical plates form 12 symmetrical sectors and provide a uniform flow of smoke from any direction to the central region of the smoke chamber (Fig. 1c), combined with its upper level, in which an optocoupler is installed, thus effectively protected from dust and from external illumination. The inner wall of the upper level of the smoke chamber was also constructed for the first time from 12 "traps" of LED radiation, cylindrical cells with a minimum level of re-radiation are black body simulators (Fig. 1 b). This reduces the level of the reflected signal of the LED, provides a low background signal of the receiver when dust accumulates on the chamber walls, and provides reliable protection against external illumination.

Light-emitting diode. To ensure low current consumption at high radiation brightness, a high-performance GaAlAs IR LED TSAL6100 of the American company Vishay Semiconductors was chosen for the new IP 212-3SU detector for special applications, including for smoke detectors. The highest technological level of production provides stability of characteristics at long terms of operation. This eliminates the effect of desensitization during operation, which often occurs when cheap, widely used LEDs are used in detectors. A distinctive feature of the TSAL6100 LED is a narrow beam pattern of ±10° and high radiation brightness, thanks to which the detector is able to detect even low levels of smoke. The high efficiency of the LED provided a low current consumption of 50 μA despite the pulse period of 1 s and an excellent response to exceeding the threshold - no more than 5 s!

A photodiode, or rather a photodetector, is our own unique development. IP 212-3SU is the only detector in which the photodiode crystal is made on the same carrier as the signal amplifier (Fig. 1a), which provides higher protection against electromagnetic interference than photodiode shielding. The amplified output signal of the photodetector has a much larger value compared to interference effects. The use of a two-level smoke chamber made it possible to reduce the length of the leads of the photodetector and further reduce the induced noise. The directivity of the photodetector is consistent with the shape of the smoke chamber.

Testing. Smoke detectors often use primitive methods of testing with a “screwdriver” or a button with unacceptably low reliability of the results: the detector can pass the test, but not respond to smoke. To ensure high testing efficiency in the new IP 212-3SU detector, the performance of all main elements, including optocouplers, is monitored by lowering the response threshold when the test button is pressed.

Detector design. The new IP 212-3SU detector has optimal dimensions Ø 88.5 × 49.5 - relatively small, not conspicuous, but not so small and streamlined that weak streams of smoke do not fall into it in the early stages of a fire. The indication LED is located in such a way that its all-round visibility is ensured in the event of a detector triggering. The design of the detector socket has also been carefully designed: the location of the contact group provides a large free area for ease of installation when using fire-resistant FRLS and FRHF cable. A “fifth contact” is provided for connecting a current-limiting resistor in series with the detector and a contact for connecting a remote indicator.

Specifications

Detector sensitivity, dB/m, range 0.05 ÷ 0.2
Supply voltage, V, 9 ÷ 28
Current consumption in standby mode, µA, no more 50
Current consumption in the "FIRE" mode, mA, range 18 ÷ 25
Degree of protection of the shell IP 30
Operating temperature range, 0 С minus 40 ÷ plus 55
Relative humidity, % 93% at + 40 0 ​​С
Weight, kg, no more 0.1
Dimensions (diameter/height), mm, no more 88.5×49.5
Degree of rigidity in terms of resistance to radio frequency electromagnetic field (GOST R 51317.4.3) 3
Average service life, years, not less 10

Wiring diagram

Scheme of inclusion for the definition of "Fire" for one detector.

Scheme of inclusion for the definition of "Fire" by two detectors.

The scheme and ratings of the terminal device are determined by the manufacturers of the control panel.

R add. calculated by the formula Radd. =(Ushs -Urest.) /Iam.,

where Ushs- loop voltage,

Ures.- voltage at the detector terminals when triggered,

Isp.- current in the detector circuit, determined by the control panel as a signal "Fire".

Certificate

The passport

INTRODUCTION
This passport IRSE 425.231.000 PS applies to the IP212-ZSU fire detector (hereinafter referred to as the detector) and is intended to study its design, installation, operation, transportation and storage.
2. PURPOSE
2.1. The detector IP 212-3SU is designed to detect fires accompanied by the appearance of smoke in enclosed spaces of buildings and structures for various purposes.
2.2. If smoke occurs in the area where the detector is located, it generates an electrical signal about a fire that has occurred, which is recorded by the control panel.
2.3. Announcer IP 212-3SU not. responds to changes in a wide range of temperature, humidity, background illumination from natural or artificial light sources.
2.4. When installing the detector in rooms with suspended ceilings, it can be used to simultaneously protect both under- and above-ceiling space.
2.5. The detector is designed for round-the-clock and continuous operation with control panels, domestic and imported, providing a supply voltage in the loop in the range from 9 to 28 V and perceiving a signal about the operation of a fire detector in the form of an abrupt decrease in internal resistance in direct polarity to a value of less than 450 Ohm. For example, with an addressable fire alarm control panel PPKP 019-128-1 "Rainbow-2A", with a control panel control panel PPK-2, with a signal and start fire alarm device USPP 01L Signal-42-01, with a control panel for security - fireman PPKOP0104059-4-1/01 "Signal VK" and others.
The electrical power supply of the detector and the transmission of the "Fire" signal are carried out via a two-wire alarm loop. Activation of the detector is accompanied by the inclusion of an optical indicator built into it.
The detector has a built-in overload protection when triggered, which limits the current flow through the detector to a maximum value of 30 mA.
2.4. The detector is designed for continuous operation at an ambient temperature of minus 40 to plus 60°C and relative humidity up to 95±3% at 35°C.
2.5. The degree of protection of the detector shell is IP30 according to GOST 14254-80.
1.6. The detector belongs to products with periodic maintenance.

TECHNICAL DATA IP 212-3SU

3.1. The sensitivity (activation threshold) of the detector corresponds to the concentration of smoke, which ensures the attenuation of the luminous flux in the range from 0.05 to 0.2 dB/m.
3.2 When the IP 212-3SU detector is installed in a false ceiling, it provides the possibility of simultaneous protection of the volumes under and above the suspended ceiling with an interceiling space height of up to 1 m.
3.3. The detector has a built-in optical indication of operation and provides the ability to connect a remote optical alarm.
3.4. The electrical power supply of the detector is carried out with a constant voltage of 9 - 28 V with a possible polarity reversal of the supply voltage for up to 100 ms with a repetition rate of not more than 1.5 Hz.
3.5. The output electrical signal of the detector actuation is formed by an abrupt decrease in the internal resistance to a value of not more than 450 0 m when a current of 20 ± 2 mA flows through the detector.
3.6. The output signal of the detector operation is stored during short-term single and periodic interruptions in its power supply with a duration of not more than 100 ms. The frequency of repetition of breaks is not more than 1.5 Hz.
3.7. The detector operation signal is stored after the end of exposure to combustion products. The minimum holding current of the detector in the triggered state is 5 mA. Resetting of the triggering signal is carried out by polarity reversal or switching off the power supply of the detector for a period of at least 2.5±0.5 s.
3.8. IP 212-3SU detector does not work during short-term single or periodic interruptions in its power supply with a duration of not more than 100 ms with a time interval between them of at least 0.7 s.
3.9. The maximum allowable backlight value is 12,000 lux.
3.10. The power consumed by the detector in standby mode at a nominal voltage of 20 V is not more than 0.003 W.
3.11. The current consumed by the detector in standby mode at a maximum supply voltage of 28 V is not more than 0.11 mA.
3.12. The current consumed by the detector when powered by reverse polarity voltage is not more than 5 µA.
3.13. The weight of the detector with the socket is not more than 0.35 kg.
3.14. The overall dimensions of the detector with a socket are not more than 100 x 100 x 70 mm.
3.15. The detector IP 212-3SU works stably under the conditions of climatic influences:
temperature from minus 40 to plus 60°С; relative air humidity up to 98% at a temperature of 35 C without moisture condensation on the structural elements of the detector; air flow at speeds up to 10 m/s.
3.16. The norm of the average time between failures of the detector, taking into account technological maintenance, is 60,000 hours.
3.17. The average service life of the detector is at least 10 years.

One of the novelties in this direction is the device IP 212-3SU. In terms of its technical characteristics, it surpasses its predecessors.

Application area

The IP 212-3SU device (photo below) detects a fire by detecting solid particles of soot and evaporation products of liquids in the air. It is part of the fire protection system. Therefore, it can be used in conjunction with other detectors, fire extinguishing systems, video cameras.

IP 212-3SU can be installed almost anywhere. The detector manual distinguishes the following types of rooms:

  • Premises of residential, administrative and economic buildings.
  • In basements, building entrances.
  • On sea vessels (cruise, military, and so on).
  • In train cars.
  • In industrial premises (warehouses, hangars, storage facilities, etc.).
  • In public buildings (schools, kindergartens, entertainment centers, shopping centers).
  • In places where pets are kept and other premises for agricultural purposes.
  • In garages, closed parking lots.

This is not a complete list of places where the sensor can be installed. It can be installed in all enclosed spaces.

The device is mounted on ceilings with a surface of various nature: concrete, wood, plastic, plasterboard, stretch ceilings, steel supports or even metal cables (cables). Manufacturers recommend not to install the device in the corners of the room. This is due to the fact that the smoke gets there last.

Device and principle of operation

Reliable operation is ensured by the simple design of the detector. The IP 212-3SU sensor includes the following elements:

  • Sturdy white plastic housing.
  • Smoke chamber with two levels. It allows smoke into the case, but protects the internal elements of the product from light.
  • A board that processes the received electrical signal. Another of its functions is to control the device as a whole.
  • Permanently on LED. It is supplemented with an amplifier, due to which even a small concentration of smoke is determined. Its light is in the form of a beam, which is reflected from soot particles in the air in case of smoke.
  • A photodiode that captures the reflected beam of an LED and converts it into an electrical impulse.
  • Light indicator.

In the event of smoke, the light pulse of the LED is reduced. This leads to a change in the electrical parameters of the photodiode. These changes are recorded and processed electronically. The signal is then transmitted to the control device. After the alarm is triggered, you can turn it off by simply turning off the power.

Technical parameters of the device

IP 212-3SU sensor has the following characteristics:

  • Weight - 100 grams.
  • Case diameter - 89 millimeters.
  • The height of the device is 50 millimeters.

  • Able to work at temperatures from minus 40 to plus 60 degrees.
  • Works at air humidity up to 98%.
  • Power is supplied by direct current (9-30 volts).
  • It takes 5 seconds to detect smoke.
  • The service life reaches 10 years.

Thanks to these characteristics, the IP 212-3SU device has become widespread.

Installation and maintenance of the sensor

Long service life is ensured by the correct installation and operation of the IP 212-3SU device. The instruction manual included in the kit will help you do everything right.

The installation of the detector includes the following steps:

  • Determination and marking of the place where the device will be installed.
  • Preparation of holes for fixing the case.
  • Fixing the device in place.
  • Connecting the alarm loop.
  • Power connection.
  • Checking the correct connection of the device. For this, a probe or a special aerosol can be used.

The quality of the device depends on the conditions of its operation and maintenance. The detector must be checked every six months. Maintenance consists of the following procedures:

  • Keeping the housing clean from dust and dirt.
  • Dust removal of the smoke chamber and other elements. Do this with airflow.
  • Checking the reliability of the wire connection.
  • Trial test of the sensor.

The IP 212-3SU detector cannot be used in polluted air conditions. Therefore, when performing construction and repair work, it must be turned off.

Probably every owner wants his house, dacha and even industrial premises to always be under reliable control and protection. It is for such purposes that there is a fire detector SP 212-3su. This sensor gives a signal when a fire is detected and when there is minimal smoke, within the radius of its work.

The detector ip 212-3su is the embodiment of twenty years of experience in the production and design of fire detectors.

If smoke appears within the operating radius of the device, an electrical signal is generated, which is transmitted to the control panel. If you decide to install this model on a suspended ceiling, then it will protect both the under- and above-ceiling space.

Installation ip 212 3su

Innovation of the model ip 212-3su

The lower part of the smoke chamber catches horizontal smoke flows that spread along the ceiling. The LED, which was used in IP 212-3su, has a narrow radiation pattern, which, together with bright radiation, detects even minimal levels of smoke. The response threshold in this case is no more than 5 seconds. The photodiode crystal is on the same carrier along with signal amplification. This is the only sensor made in this way and with it the protection against electromagnetic interference is greatly increased.

The model is characterized by high sensitivity and the absence of false positives. It was these achievements that brought the un 212-3su to the first places in sales. He has patents for "industrial design" and "utility model".

A small, compact device manufactured with dimensions of 88.5x49.5. It is almost imperceptible, but at the same time, despite the same size, it quickly catches even the smallest streams of smoke when the fire has just begun. Ease of installation due to the good location of the contact group.

Wiring diagram ip 212 3su

Key Benefits

  • Does not respond to interference.
  • Maximum dust protection.
  • During the standby mode, it consumes the minimum amount of current.
  • Convenient and most accurate testing.
  • Operating temperature -40 +55 degrees Celsius.
  • Easy and affordable installation.
  • Possibility of mounting in suspended ceilings.

This number of advantages significantly distinguishes the fire detector ip 212-3su among other sensors.

manufacturer's warranty

The manufacturer has established such warranty periods as 18 months after putting it into operation, but not more than 24 months from the date of manufacture. During the warranty period, all repairs of the detectors are carried out by the manufacturer. In such a case, the warranty period may be extended by the period that was spent repairing the defect. The warranty case occurs when the consumer has used the sensor in accordance with the instructions for use, storage and transportation.

Storage and operation

The detectors are stored in closed warehouses, in original packaging. Mandatory storage conditions protect devices from sunlight, moisture, mold.

When checking the service life of the devices, it was found that the failure time is about 60,000 hours, within 10 years.

Results

After listing all the advantages and innovations in the SP 212-3su model, we can safely say that choosing this model will not make you upset. Simplicity of appearance, the possibility of installation in false ceilings with the possibility of protecting the interceiling space, protection from dust - all these are the minimum transfers of the updated version of the fire detector. The most important advantage still remains that the sensor reacts even to minimal smoke and immediately transmits an “alarm” signal. Such a basic element as a fire alarm is constantly improving along with the quality and duration of its work.

Fire, which is a friend of man, in an instant can turn into a ruthless element that destroys everything around. It is not always possible to prevent fires at various facilities due to various objective and subjective factors. Identification of the primary signs of a fire is quite accessible if potentially fire-hazardous premises are equipped with various signal sensors and detectors. In the course of many years of improvements and improvements, the smoke detector IP 212-3SU was created - a unique device that registers the onset of a fire at the earliest stages.

Purpose and scope

The purpose of this device is to detect the presence in the air of signs of a fire, namely, solid particles of soot and products of evaporation of combustible liquids suspended in the air. The sensor works in the general system of fire and security systems and can be used in combination with other sensors, video cameras and fire extinguishing systems.

The device is powered from the loop of the security system. The detector has a narrow specialization and is not susceptible to heat and all kinds of radiation.

You can use it by installing in such places:

  • in the rooms of residential, economic and administrative buildings;
  • in the cabins of cruise ships and warships;
  • in passenger railway cars;
  • in basements and entrances of multi-storey buildings;
  • in warehouses and storages of all types of materials;
  • in kindergartens and schools;
  • in hangars of any type;
  • in cowsheds, pigsties, granaries and other premises for agricultural purposes;
  • in shopping and entertainment centers;
  • in garages and underground parking lots.

The list of these objects can be continued for a long time, since the IP 212-3SU sensors can be installed without limitation in any closed type premises. At the same time, it does not matter what microclimate is in these rooms. Sensors can be installed both in a store in the south of the country and in an unheated warehouse in the far north.

Device and principle of operation

The IP 212-3SU fire detector has a simple, but at the same time, quite effective design.

It consists of the following parts and devices:

  • housing made of durable white plastic;
  • a two-level smoke chamber with a system of internal partitions, which ensures unhindered entry of smoke into the building, without letting light into it from the outside;
  • a printed circuit board that receives and processes electrical signals and controls the device;
  • LED continuously emitting a beam;
  • a photodiode, whose task is to receive the reflected beam and convert it into a certain electrical impulse;
  • indicator light.

A feature of the improved fire detector IP 212-3SU is the installation of a high-brightness LED with an amplifier. Thanks to him, smoke is indicated at an insignificant concentration.

On a note: To avoid false signals due to dust and insects, the case is equipped with a fine safety net.

The design of the smoke chamber is also unique, which allows smoke to enter the optical system, regardless of the direction of its movement.

The principle of operation of the product is based on a change in the electrical parameters of the photodiode when the light pulse is weakened. This change is recorded and processed by electronics and transmitted as digital information to the control device. The alarm is reset by turning off the power.

Features and advantages of the device

The improved IP 212-3SU smoke detector was manufactured taking into account many years of experience in operating similar products in this series.

As a result, this device has acquired such distinctive properties:

  • original body shape design;
  • resistance to various interferences;
  • immunity to temperature changes;
  • protection against radiation of any kind;
  • unique shape of smoke chamber gratings;
  • energy efficiency;
  • high rate of smoke detection;
  • the ability to work with different types of loops, thanks to the fifth terminal for an additional resistor;
  • wide operating temperature range.

In addition, the installation of the device has become more convenient and faster thanks to the well-thought-out mechanism of the wire clamps.

Main technical characteristics

The latest models of the IP 212-3SU detector have the following indicators:

  • price - 300-400 rubles;
  • size - 89×50 mm;
  • weight - 100 gr.;
  • temperature range - from -40° С to +60° С;
  • supply voltage - direct current 9-30 V;
  • permissible air humidity - up to 98%;
  • smoke detection time - up to 5 sec;
  • service life - 10 years.

Due to these characteristics, the device is in demand for the equipment of many security and fire systems.

Installation and maintenance

Installation work on the installation and connection of smoke detectors is carried out in compliance with safety measures in accordance with the instructions for the product. Thanks to the design of the smoke chamber, the sensor can be installed in any position.

Places for installation

The surface for mounting the sensor can be:

  1. Concrete slab. Plastic dowels and self-tapping screws are used as fasteners.
  2. Wooden ceiling. Wood screws are used.
  3. Suspended ceiling made of plastic or plasterboard. The sensors are attached through the cladding to the crate with metal screws.
  4. Stretch ceiling. Fasteners are carried out to embedded parts with screws corresponding to their material.
  5. Steel columns, beams and supports. The best option is to fasten with bolts and nuts through through holes.
  6. Steel cables and power cables. The sensor is fixed, either with non-ferrous metal wire, or on special clamps.

Avoid mounting appliances in the corners of rooms where smoke is the last to enter.

Mounting the detector

The installation of the device is carried out in accordance with the general scheme of the security and fire system.

It is carried out in the following sequence:

  1. Carrying out the marking of the surfaces on which the devices will be installed.
  2. Drilling holes for mounting.
  3. Fixing sensors in place.
  4. Connecting the wires of the alarm loop to the detectors.
  5. Leading the wires from the sensors to the junction box and connecting the power supply.
  6. Checking the functionality of the detectors. The check is carried out using a test aerosol or a probe introduced into the technological hole on the body.

When planning and projecting, the area that can be controlled by one device should be taken into account.

Instrument Maintenance

Reliable and trouble-free operation of the smoke detector is possible only if the operating rules and timely maintenance are observed.

Maintenance of sensors should be carried out at least once every 6 months.

It consists of the following steps:

  • cleaning the outer surface from dirt and dust;
  • removal of accumulated debris from the smoke chambers with the help of a jet of air;
  • cleaning the LED and photocell;
  • checking the reliability of the wire connection;
  • device performance testing.

Before carrying out repair work, it is recommended to remove the sensors. Contact with mortar, chemically active liquids can cause metal corrosion and a violation of the aerodynamic qualities of the smoky box. In addition, sensors can be broken by heavy repair equipment.

During repair, the detectors must be stored in a dry room, in a package. After installation, their performance is checked without fail.

Smoke detector video